WIKA A2G-55 User Manual

Page 6

Advertising
background image

WIKA operating instructions air2guide model A2G-55

GB

Uv Out Gnd

Uv Out Gnd

Loop

6

40317650.01 09/2010 GB/D/F/E/I

5. Installation / 6. Commissioning / Electrical connections

6. Commissioning / Electrical connections

Output signal

DC 0 … 10 V, 3-wire

optionally 4 … 20 mA, 2-wire

Supply voltage

DC 13 ... 32 V

Electrical connection

PG-gland M16

Screw terminals max. 1.5 mm²

Connection diagram

5. Installation

■

Protect measuring instruments from contamination, high tempera-

ture changes and vibrations

■

In order to avoid any additional heating, the instruments must not be

exposed to direct solar irradiation while in operation.

■

The differential pressure transmitter must be screw-fitted on a

suitable vertical surface. The instrument has to be mounted horizon-

tally using the enclosed mounting screws.

Legend

Pin 1: Power supply (+)

Pin 2: Output signal

Pin 3: Ground

Legend

Pin 1: Loop +

Pin 3: Loop -

Output signal 4 … 20 mA, 2-wire

Output signal DC 0 … 10 V, 3-wire