WIKA operating instructions pressure switch model PSD-3x

GB

11430486.06 02/2012 GB/D/F/E

6. Commissioning, operation

Connection diagrams

Zero point adjustment

Check the indicated zero point on the display during commissioning.

Should an offset be displayed as a result of installation, this can be reset in programming mode with the

0SET parameter

■

Carry out zero point adjustment for relative and vacuum pressure measuring ranges in a

depressurised state.

■

Carry out zero point adjustment of absolute pressure ranges from 0 bar absolute

(vacuum). Since appropriate references are required for this, we recommend that this is

only carried out by the manufacturer.

6.2 Making the electrical connection

■

The instrument must be earthed via the process connection!

■

The power supply for the pressure switch must be made via an energy-limited electrical circuit in

accordance with section 9.3 of UL/EN/IEC 61010-1 or an LPS to UL/EN/IEC 60950-1 or class 2 in

accordance with UL1310/UL1585 (NEC or CEC). The power supply must be suitable for operation

above 2,000 m should the pressure switch be used at this altitude.

■

For cable outlets, make sure that no moisture enters at the cable end.

Circular connector M12 x 1; 4-pin

Assignment

U

+

U-

S

+

SP1

SP2

1

3

2

4

2

Circular connector M12 x 1; 5-pin

Assignment

U

+

U-

S

+

SP1

SP2

1

3

5

4

2