WIKA operating instructions pressure transmitter, model S-11

GB

14043046.01 06/2012 GB/D/F/E

7. Adjustment of zero point ... / 8. Maintenance and cleaning

7.4 Finish the adjustment (figure A)

■

Disconnect the instrument connector

from the power supply and the display unit.

■

Carefully push the instrument connector

onto the instrument, without damaging the wires or the

seals. The seals must be clean and undamaged in order to guarantee the given ingress protection.

■

Tighten the clamping nut

.

After the adjustment, check that the system is functioning correctly.

Recommended recalibration cycle: 1 year

8. Maintenance and cleaning

8.1 Maintenance

This pressure transmitter is maintenance-free.

Repairs must only be carried out by the manufacturer.

8.2 Cleaning

CAUTION!

■

Before cleaning, correctly disconnect the instrument from the pressure supply, switch it

off and disconnect it from the power supply.

■

Do not use any pointed or hard objects for cleaning, as they may damage the diaphragm

of the process connection.

■

Clean the instrument with a moist cloth.

■

Electrical connections must not come into contact with moisture.

■

Wash or clean the dismounted instrument before returning it in order to protect personnel

and the environment from exposure to residual media.

■

Residual media in the dismounted pressure transmitter can result in a risk to persons,

the environment and equipment. Take sufficient precautionary measures.

For information on returning the instrument see chapter 10.2 "Return".