6 Commissoning, operation

WIKA operating instructions, model A-AI-2

17

A-AI-2-1:

description

to select as
output

output (out)

see chapter

no output, device is
used as display

no

off --

2-point-controller

2P

switching function

6.3.1

Min/Max alarm

AL

min/max alarm, inverse

6.3.2

A-AI-2-S:

description

to select as
output

output 1 (out 1)

output 2 (out 2)

see chapter

no output, device is
used as display

no

off off --

2-point-controller

2P

switching
function

off

6.3.1

Min-/Max-alarm,
common

AL

Min-/Max-alarm,
inverted

off 6.3.2

3-point-controller

3P

switching
function 1

switching
function 2

6.3.1

2-Punkt-Regler with
Min-/Max-alarm

2P.AL

switching
function 1

Min/Max alarm,
inverted

6.3.1

Min-/Max-Alarm,
individual

AL.F2

Max alarm,
inverted

Min alarm,
inverted

6.3.2

Press button 1 to validate the selected output function. The display shows “outP“ again.

For output function = no the configuration is now finished. Press button 1 to finish the adjustment and
to switch over to display the measuring value.

If the output function was changed here, the delay and preferred state of switching function and the
switching points / alarm-boundaries are to configured in following.

Hint:

The settings described in the following depend on the selected output function.
Depending on this setting therefore it is possible that more than one point is not
present in the following.

When pressing button 1 again, the device will display “1.dEL“ (delay = delay of switching

function 1).

Use button 2 and button 3 to set the desired value for the switching-delay.

Hint: the selected value [0.01 ... 2.00] accords the switching delay in seconds.

Press button 1 to validate the selection. The display shows “1.dEL“ again.
When pressing button 1 again, the device will display “1.Err“ (error = preferred state of

switching function 1).

Use button 2 and button 3 to set the desired initial state in case of an error.