8 faults – WIKA A-AI-2 User Manual

Page 23

Advertising
background image

8 Faults

WIKA operating instructions, model A-AI-2

23

8 Faults


When detecting an operating state which is not permissible, the device will display an error code. The
following error codes are defined:

Fehler

presumed cause

solution

Err.1
Exceeding of the measuring
range

Input signal too high
Sensor

shorted

The input signal must be

within the limits

Check

sensor,

transducer/transmitter

Check device configuration

Err.2
values below measuring range

Input signal zu low
Current below 4 mA

The input signal must be

within the limits

Check

sensor,

transducer/transmitter

Check device configuration

Err.3
display range has been
exceeded

incorrect

scale

The input signal must be

within the limits

scale

smaller

indication

range

Err.4
values below display range

incorrect

scale

The input signal must be

within the limits

scale

smaller

indication

range

Err.7
System error

valid

operation

temperature

has been exceeded

defective

device

Stay within valid temperature

range

Exchange the defective

device

Err.11
value could not be calculated

incorrect

scale

Check settings and input

signals


CAUTION!
If faults cannot be eliminated by means of the measures listed above, the instrument
must be shut down immediately, and it must be ensured that pressure and/or signal
are no longer present, and it must be prevented from being inadvertently put back
into service. In this case, contact the manufacturer.


If a return is needed, please follow the instructions given in chapter "9.2 Return".