IN-IVSP/QS-10

Foot Switch Operation (Run/Stop mode):

To use the controller with a standard “dry contact” switch to control Start/Stop and direction the following
settings should be made.

1. Set F_10 to 1 ***
2. Connect pin 3 to Pin 5 of TM2. Motor will start to accelerate until set frequency is reached.
3. Direction can be controlled by via TM2 pin 4 to TM2 pin 5.

a. TM2 pin 4 open spins motor in the Forward direction
b. TM2 pin 4 connected to TMP2 pin 5 TM2 pin 4 open spins motor in the Reverse direction



Analog Frequency (Speed) Command:

To control the frequency (speed) of the motor via 0 – 10 VDC, 0 – 20 mA or 4 – 20 mA the following
settings should be made.

1. Control type setting (F_11) ***

a. For 0 – 10 VDC / 0 – 20 mA input set F_11 to 1
b. For 4 – 20 mA set F_11 to 2

2. Input control signal into TM2 pin 9

a. For FM_11 = 1 use 0 – 10 VDC or 0 – 20 mA
b. For FM11 = 2 use 4 – 20 mA

3. Command Start via Keypad


Restore Factory Default Settings:

To return the drive to a factory default, perform the following steps.

1. Restore factor fault (F_25) ***

a. For 50 Hz system set F_25 to 10
b. For 60 Hz system set F_25 to 20


*** To Change Function (F_) value:

Press

to get to desired function

Press

to select desired function value

Press

to select function

Press

to select function value

Press

to accept value