15 cooling, 16 specifications – ADC PowerWorx Power Distribution Products User Manual

Page 14

Advertising
background image

ADCP-80-545 • Issue 3 • March 2006

Page 8
© 2006, ADC Telecommunications, Inc.

Two breaker alarm indicators (red LED) are provided on the front side of the panel. A separate
breaker alarm indicator is provided for each of the two power output buses (A and B). The
breaker alarm indicator turns on if any circuit breaker on the corresponding power bus trips.
The breaker alarm indicator turns off when the tripped breaker is placed in the on position. The
breaker alarm indicators cannot be field-replaced.

1.15 Cooling

The Select Series circuit breaker panel relies on convection air flow for cooling. Holes are
provided on the top and bottom of the panel to allow heated air to escape from the panel and
cool air to enter. At least one rack unit of space must be provided above and below the panel to
allow for air circulation.

1.16 Specifications

The specifications for the Select Series circuit breaker panel are listed in

Table 2

.

Table 2. Circuit Breaker Panel Specifications

PARAMETER

SPECIFICATION

REMARKS

Physical

Weight

10 lbs. (4.54 kg)

Dimensions (HxWxD)

1.73 x 17.13 x 11.11 inches
(43.9 x 435 x 282 mm)

See

Figure 3

Color

Putty white

Rack mounting

19- or 23-inch

EIA or WECO hole spacing

Electrical

Operating voltages

–24 Vdc
–48 Vdc

–21 to –30 Vdc tolerance

–42 to –56 Vdc tolerance

Input current

100 Amps per bus maximum

Breaker type

Magnetic actuation, manual
reset, replaceable

1- pole or 2-pole

Breaker mounting positions

Eight 1-pole per bus (16 total) or
Four 2-pole per bus (8 total

Or any combination of 1- and 2-
pole breakers

Maximum breaker size

50 Amps

Input terminal type

2-hole compression lug

0.625 inch between centers

Output terminal type

Screw down terminal (8-32)

Max lug width 0.378 inches

Alarm terminal type

Screw down terminal (3-48)

Max lug width 0.20 inches

Alarm contact voltage

110 Vac, 125 Vdc maximum

Alarm contact current

1 Amp maximum

Grounding connections

Two #10 studs

#10 ring terminals