Silent Call Gentex 9120FT User Manual

Photoelectric smoke alarm

Advertising
background image

Standard Features

• Available in 120VAC and 220VAC with 9VDC battery back-up
• Horn frequency 3100 Hz (nominal)
• Nominal 2.5% sensitivity
• Patented three position test switch
• Relays operate on battery back-up
• Quick-disconnect wiring harness
• 90dBA continuous piezo horn (9120/9220 Series)
• 90dBA temporal 3 evacuation piezo horn (9123/9223 Series)
• 5-to-1 signal-to-noise ratio
• Pulsing LED sensing chamber
• Fully insect screened
• Interconnect with all Gentex tandem capable smoke alarms
• Easy Wash

TM

on-site maintenance washing program

• Red LED pulses every 30 seconds, green LED for AC power on
• Mounting hardware adapts to standard junction boxes
• Dust cover to prevent contamination during installation
• Low or missing battery indicator
• 1 year warranty from date of purchase

• UL 217 and UL 1730 Listed
• CSFM #7257-569:117
• BS+A/MEA #285-91-E
• BFP (City of Chicago)
• MSFM Listing #1929
• Hong Kong FSD Listed (9220 Series ONLY)

Photoelectric Smoke Alarm

120VAC and 220VAC with 9VDC Battery Back-Up
Single/Multiple Station Smoke Alarm

Product Listings

Applications

The 9000/9003 Series of photoelectric smoke alarms is designed for
residential and commercial residential applications, including homes,
apartments, hospitals, hotels and motels, in compliance with UL 217,
UL 1730 applicable IBC/IFC Standards and NFPA 72.

Available in many different models, the 9120/9123 Series is engi-
neered to virtually eliminate nuisance alarms and deliver outstanding
performance wherever reliable fire protection is required. The 9000/
9003 Series is provided with a 9VDC alkaline battery for back-up in
the event building power is lost. The battery impedance is verified
and the alarm provides a low or missing battery warning.

The Gentex 9000/9003 Series provides an exclusive patented three
position test feature that simulates a 0.85% and 3.5% actual smoke
condition in full compliance with NFPA 72 and UL Standards.

Options include self-restoring 135°F integral or isolated heat
thermals and Form A/Form C dry contacts for remote annunciation.
Tandem interconnection of up to 12 units is available on several
models; tandem interconnection of up to 6 units is available on “F”
models, which activate the dry contacts from the tandem wire or a
local alarm.

• NFPA 72
• IBC/IFC/IRC

Product Compliance

Easy Wash

TM

-

On Site
Maintenance
Program

9 0 0 0 /

9 0 0 3

S E R I E S

Advertising