Smoke alarm, Tandem wiring diagram relay models, Isolated thermal with optional accessory contacts – Silent Call Gentex 9120FT User Manual

Page 3

Advertising
background image

120 VOLTS
60 HZ

RED / YEL

WHT

BLK

SUPERVISION

WIRES

ACCESS

CONTACTS

ALARM

CONTACTS

TANDEM

POWER

CAUTION:
RED/YELLOW wire to be capped
when not in use. This wire is for
tandem connection only. Do not
connect to any other circuit.

9000/9003 Series Wiring Diagrams

ELECTRICAL
BOX

QUICK
DISCONNECT
TYPE PLUG

SMOKE
ALARM

1

2

3

T

ANDEM WIRE

NEUT

HOT

TO ADDITIONAL
GENTEX SMOKE ALARMS

LIMITATIONS:
Maximum of 12 alarms
(9120/9123, 9120/9123T,
9120/9123H, 9220/9223,
9220/9223T, 9220/9223H)
may be connected together.
Do not exceed 125 feet
between each detector. Do
not exceed 1125 feet
between the first and last
alarm. NOTE: Gentex smoke
alarms can not be intercon-
nected to detectors from
other manufacturers.

A MAXIMUM OF SIX (6)
ALARMS WITH A RELAY
MAY BE TANDEM
INTERCONNECTED.
(9120/9123F, 9120/9123TF,
9120/9123HF, 9220/9223F,
9220/9223TF, 9220/9223HF)

Tandem Wiring Diagram

Relay Models

GRAY

GRAY

YEL

ORN

BLU

VIO

VIO/BLK

RED/YEL

BLK

WHT

RELAY CONTACTS
RATED LOAD RESISTIVE
1.0 AMP @ 24 VDC
0.6 AMP @ 125 VAC MAX
0.3 AMP @ 220 VAC MAX

Models
9120/9123F
9120/9123TF
9230/9223F
9220/9223TF

Isolated Thermal with
Optional Accessory Contacts

HF ONL

Y

SMOKE
ALARM

HEAT
SENSOR

ACCESS
CONTACTS

ALARM
CONTACTS

TANDEM

POWER

SMOKE
ALARM

SMOKE
ALARM

1

2

3

1

2

3

ELECTRICAL
BOX

ELECTRICAL
BOX

Models
9120/9123H
9120/9123HF
9220/9223H
9220/9223HF

BRN

BRN
GREY
GREY

YEL

ORN

BLU

VIO

VIO/BLK

RED/YEL

BLK

WHT

Advertising