Safety warnings for kitchen unit installer

When used as an extractor unit, the hood must be fitted

with a 120mm diameter hose.

If the fumes must be forced out through the wall, you

must obtain a MKZ sizable wall exhaust pipe (with

external exhaust and air intake), E-Nr.- 610 899 004 (Ø 120

mm) which is one of our optional parts.

When installing the hood, make sure you respect

the following minimum distance from the top edge

of the cooking hob/ring surfaces:

electric cookers

600 mm

gas cookers

650 mm

coal and oil cookers

700 mm min.

The air outlet must not be connected to chimney flues or

combustion gas ducts. The air outlet must under no cir-

cumstances be connected to ventilation ducts for rooms in

which fuel-burning appliances are installed.

It is advisable to apply for authorization from the relevant

controlling authority when connecting the outlet to an

unused chimney flue or combustion gas duct.

The air outlet installation must comply with the

regulations laid down by the relevant authorities.

When the unit is used in its extractor version, a

sufficiently large ventilation hole must be provided, with

dimensions that are approximately the same as the outlet

hole.

National and regional building regulations impose a

number of restrictions on using hoods and fuel-burning

appliances connected to a chimney, such as coal or oil

room-heaters and gas fires, in the same room.

The national decree on fuel-burning systems specifies a

maximum depression of 0.04 bar in such rooms.