9. If a greasy residue is present on blower wheel, remove

wheel from the blower housing and wash it with an
appropriate degreaser. To remove wheel:

a. Mark blower wheel location on shaft before disassembly

to ensure proper reassembly.

b. Loosen setscrew holding blower wheel on motor shaft.

NOTE:

Mark blower mounting arms, motor, and blower housing

so motor and each arm is positioned at the same location during
reassembly.

c. Mark blower wheel orientation and cutoff plate location

to ensure proper reassembly.

d. Remove screws securing cutoff plate and remove cutoff

plate from housing.

e. Remove bolts holding motor and motor mounts to

blower housing and slide motor and mounts out of
housing. Disconnect capacitor and ground wire attached
to blower housing before removing motor. Motor mount
belly band need not be removed unless motor is to be
replaced.

f. Remove blower wheel from housing.

CAUTION:

The blower wheel should not be dropped or

bent as balance will be affected.

10. Reassemble motor and blower by reversing items 9a

through 9f. Be sure to reattach ground wire.

11. Reinstall blower assembly in furnace.

12. Reinstall control and transformer support assembly in

furnace.

13. Reconnect blower leads to furnace control and auxiliary

limit switch leads (downflow only).

Refer to furnace wiring diagram, and connect thermostat
leads if previously disconnected. (see Fig. 12.)

NOTE:

Refer to Table 3 for motor speed lead relocation if leads

were not identified before disconnection.

CAUTION:

Heating air speed selection MUST be ad-

justed to provide proper air temperature rise as specified
on the rating plate. Failure to adjust the heating speed
may shorten heat exchanger life.

14. Downflow furnaces only: Reinstall internal vent pipe and

enclosure by reversing items 3a through 3d.

NOTE:

A releasing agent such as PAM cooking spray or equiva-

lent (must not contain corn or canola oil, aromatic or halogenated
hydrocarbons or inadequate seal may occur) and RTV sealant
(G.E. 162, 6702, or Dow-Corning 738) are needed before starting
installation. DO NOT substitute any other type of RTV sealant.
G.E. 162 (P771-9003) is available through RCD in 3-oz. tubes.

15. Reinstall vent connector to furnace flue collar. After fully

assembling vent connector to furnace flue collar, securely
fasten vent connector to flue collar with 2 field-supplied,
corrosion-resistant, sheet metal screws located 180° apart
and midway up the collar.

16. Turn on electrical supply. Manually close blower access

door switch. Use a piece of tape to hold switch closed.
Check for proper rotation and speed changes between
heating and cooling by jumpering R to W and then R to Y
on furnace control thermostat terminals.

Fig. 6—Model 383KAV Upflow

A00261

BLOCKED
VENT
SAFEGUARD

FLUE
COLLECTOR
BOX

MOUNTING

SCREWS

RELIEF

BOX

CONTROL

FILTER
RETAINER

WASHABLE
FILTER

FLUE
COLLAR

PRESSURE
SWITCH

GAS

VALVE

C

OM

24V

HUM

G

R

Y

W

Fig. 7—Model 373LAV Downflow

A99285

VENT PIPE
ENCLOSURE

BLOCKED
VENT
SAFEGUARD

MANUAL
RESET LIMIT
SWITCHES

AUXILIARY

LIMIT

SWITCH

(WHEN USED)

MOUNTING

SCREWS

RELIEF

BOX

C
OM

24V

HUM

G

R

Y

W

CONTROL

PRESSURE
SWITCH

GAS

VALVE

FLUE
COLLAR

TABLE 3—SPEED SELECTOR

COLOR

SPEED

FACTORY-

ATTACHED TO

Black

High

Cool

Yellow (When

present)

Medium-High

Spare

Blue

Medium-Low

Heat

Red

Low

Spare

White

Common

L2/COM

—4—