Bryant GAS-FIRED INDUCED-COMBUSTION FURNACES 373LAV User Manual

Page 7

Advertising
background image

c. Remove control access door.

d. BRIEFLY remove either wire from the main limit switch

until LED goes out, then reconnect it.

NOTE:

If wire to main limit is disconnected longer than 4 sec,

main blower starts, and retrieval request is ignored.

2. When above items have been completed, the following will

occur:

a. LED flashes a status code 4 times. Record this status

code for further troubleshooting.

b. Inducer motor starts and continues to run the entire

component test.

c. Hot surface igniter is energized for 15 sec, then de-

energized.

d. Main blower operates at cooling speed for 10 sec, then

turns off.

e. Main blower operates at heating speed for 10 sec, then

turns off.

f. Inducer motor stops.

Items a through e above will assist in furnace troubleshoot-
ing since all components are functionally operated except
the gas valve. This procedure is also referred to as "Com-
ponent Test."

3. Operate furnace through 1 heat cycle to test for proper

operation and check LED status.

4. If furnace is operating properly and LED indicates proper

operation, replace control access door.

5. Component Test can also be initiated by performing the

following:

a. Remove control access door.

b. Remove blower access door.

c. Manually close blower access door switch.

WARNING:

Blower access door switch opens 115-v

power to control. No component operation can occur.
Caution must be taken when manually closing this switch
for service purposes. Failure to follow this warning could
result in personal injury or death.

d. BRIEFLY short (jumper) TEST, 3/16-in. quick-connect

terminal on control (adjacent to LED diagnostic light),
and C

OM

-24V terminal on furnace thermostat connection

block. (See Fig. 11.)

NOTE:

If TEST to C

OM

-24V terminals are jumpered longer than

2 sec, LED will flash rapidly, and test request will be ignored.

e. Component Test will function as described in item 2

above.

f. Check LED status.

g. If LED status indicates proper operation, RELEASE

BLOWER ACCESS DOOR SWITCH, replace blower
access door, and replace control access door.

E.

Troubleshooting

Refer to the service label. (See Fig. 13.) Pages 10 and 11 contain
a troubleshooting guide. This guide can be a useful tool in isolating
furnace operation problems. Beginning with the word "Start,"
answer each question and follow the appropriate arrow to the next
item.

The guide will help to identify the problem or failed component.
After replacing any component, verify correct operation sequence.

Fig. 10—Heating and Cooling Application Wiring Diagram

A98521

115-V FIELD-

SUPPLIED

DISCONNECT

AUXILIARY
J-BOX

24-V

TERMINAL

BLOCK

THREE-WIRE

HEATING-ONLY

FIVE WIRE

NOTE 1

NOTE 2

FIELD-SUPPLIED
DISCONNECT

CONDENSING
UNIT

TWO
WIRE

FURNACE

C
O
N

T

R
O

L

R

G

C

W

C

R

G

Y

GND

GND

FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING

208/230- OR
460-V
THREE
PHASE

208/230-V
SINGLE
PHASE

BLOWER DOOR SWITCH

WHT

BLK

WHT

BLK

NOTES:

Connect Y-terminal in furnace as shown for proper blower operation.
Some thermostats require a "C" terminal connection as shown.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.

W

Y

GND

THERMOSTAT
TERMINALS

1.
2.
3.

—7—

Advertising
This manual is related to the following products: