Bryant Induced-Combustion 4-Way Multipoise 310AAV User Manual

Page 11

Advertising
background image

c. Combining space on different floor levels. The volumes of

spaces on different floor levels shall be considered as
communicating spaces if connected by one or more perma-
nent openings in doors or floors having free area of at least
2 in.

2

/1,000 Btuh (4,400 mm

2

/kW) of total input rating of

all gas appliances.

2. An attic or crawlspace may be considered a space that freely

communicates with the outdoors provided there are adequate
permanent ventilation openings directly to outdoors having
free area of at least 1-in.

2

/4,000 Btuh of total input rating for

all gas appliances in the space.

3. In spaces that use the Indoor Combustion Air Method,

infiltration should be adequate to provide air for combustion,
permanent ventilation and dilution of flue gases. However, in
buildings with unusually tight construction, additional air
MUST be provided using the methods described in the
Outdoor Combustion Air Method section.

Unusually tight construction is defined as
Construction with:

a. Walls and ceilings exposed to the outdoors have a continu-

ous, sealed vapor barrier. Openings are gasketed or sealed
and

b. Doors and openable windows are weatherstripped and

c. Other openings are caulked or sealed. These include joints

around window and door frames, between sole plates and
floors, between wall-ceiling joints, between wall panels, at
penetrations for plumbing, electrical and gas lines, etc.

Combination of Indoor and Outdoor Air

1. Indoor openings shall comply with the Indoor Combustion

Air Method below and,

2. Outdoor openings shall be located as required in the Outdoor

Combustion Air Method mentioned previously and,

3. Outdoor openings shall be sized as follows:

a. Calculate the Ratio of all Indoor Space volume divided by

required volume for Indoor Combustion Air Method
below.

b. Outdoor opening size reduction Factor is 1 minus the

Ratio in a. above.

c. Minimum size of Outdoor openings shall be the size

required in Outdoor Combustion Air Method above
multiplied by reduction Factor in b. above. The minimum
dimension of air openings shall be not less than 3 in. (80
mm).

INSTALLATION

UPFLOW INSTALLATION

Bottom Return Air Inlet

These furnaces are shipped with bottom closure panel installed in
bottom return-air opening. Remove and discard this panel when
bottom return air is used. To remove bottom closure panel,
perform the following:

1. Tilt or raise furnace and remove 2 screws holding bottom filler

panel. (See Fig. 9.)

2. Rotate bottom filler panel downward to release holding tabs.

3. Remove bottom closure panel.

4. Reinstall bottom filler panel and screws.

Side Return Air Inlet

These furnaces are shipped with bottom closure panel installed in
bottom return-air opening. This panel MUST be in place when
only side return air is used.

NOTE:

Side return-air openings can be used in UPFLOW and

most HORIZONTAL configurations. Do not use side return-air
openings in DOWNFLOW configuration.

Leveling Legs (If Desired)

In upflow position with side return inlet(s), leveling legs may be
used. (See Fig. 10.) Install field-supplied, 5/16 X 1-1/2 in. (max)
corrosion-resistant machine bolts, washers and nuts.

NOTE:

Bottom closure must be used when leveling legs are used.

It may be necessary to remove and reinstall bottom closure panel
to install leveling legs. To remove bottom closure panel, see Item
1. in Bottom Return Air Inlet section.

To install leveling legs:

1. Position furnace on its back. Locate and drill a hole in each

bottom corner of furnace. (See Fig. 10.)

2. For each leg, install nut on bolt and then install bolt and nut in

hole. (Install flat washer if desired.)

3. Install another nut on other side of furnace base. (Install flat

washer if desired.)

4. Adjust outside nut to provide desired height, and tighten inside

nut to secure arrangement.

5. Reinstall bottom closure panel if removed.

DOWNFLOW INSTALLATION

NOTE:

For downflow applications, this furnace is approved for

use on combustible flooring when any one of the following 3
accessories are used:

Special Base, KGASB

Cased Coil Assembly Part No. CD5 or CK5

Coil Box Part No. KCAKC

1. Determine application being installed from Table 3.

2. Construct hole in floor per Table 3 and Fig. 11.

3. Construct plenum to dimensions specified in Table 3 and Fig.

11.

4. If downflow subbase, KGASB is used, install as shown in Fig.

12. If Coil Assembly Part No. CD5 or CK5 or Coil Box Part
No. KCAKC is used, install as shown in Fig. 13.

NOTE:

It is recommended that the perforated supply-air duct

flanges be completely folded over or removed from furnace when
installing the furnace on a factory-supplied cased coil or coil box.
To remove the supply-air duct flange, use wide duct pliers or hand
seamers to bend flange back and forth until it breaks off. Be careful
of sharp edges. (See Fig. 14.)

Fig. 9—Removing Bottom Closure Panel

A02098

10

Advertising