INSTALLATION

Step 1 — Thermostat Location

Thermostat should be mounted:

S

Approximately 5 ft (1.5m) from floor.

S

Close to or in a frequently used room, preferably on an inside
partitioning wall.

S

On a section of wall without pipes or duct work.

Thermostat should NOT be mounted:

S

Close to a window, on an outside wall, or next to a door leading
to the outside.

S

Exposed to direct light and heat from the sun, a lamp, fireplace,
or other heat--radiating object which may cause a false reading.

S

Close to or in direct airflow from supply registers and return--air
grilles.

S

In areas with poor air circulation, such as behind a door or in an
alcove.

Step 2 — Install Thermostat

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury

or death.
Before installing thermostat, turn off all power to unit. There

may be more than 1 disconnect.

!

WARNING

1. Turn OFF all power to unit.
2. If an existing thermostat is being replaced:

a. Remove existing thermostat from wall.

b. Disconnect wires from existing thermostat, one at a

time. Be careful not to allow wires to fall back into wall.

c. As each wire is disconnected, record wire color and

terminal marking.

d. Discard or recycle old thermostat.

ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental

damage.
Mercury is a hazardous waste. Federal regulations require that

Mercury be disposed of properly.

CAUTION

!

3. Separate front and back (mounting base) assembly of ther-

mostat.

4. Route thermostat wires through hole in mounting base.

Level mounting base against wall (for aesthetic value only,

thermostat need not be level for proper operation) and mark
wall through 2 mounting holes.

5. Drill two 3/16--in. mounting holes in wall where marked.
6. Secure mounting base to wall with 2 anchors and screws

provided making sure all wires extend through hole in

plastic.

7. Strip 1/4 in. insulation from thermostat wire and adjust

length to reach terminal block connector on mounting base.

Match and connect proper wiring in accordance with wiring
diagrams.

8. Push any excess wire back into wall. Seal hole in wall to

prevent air leaks. Leaks can affect thermostat operation.

Any excess wire left inside thermostat casing may also af-
fect thermostat operation by interfering with airflow across

the temperature sensor.

9. Snap thermostat together making sure terminal block con-

nector aligns, and assembly is secure.

10. Turn on power to unit.

On power up, depending on the thermostat model being used, the

LCD readout will display either, AC or PC for air conditioner
model (1--stage heat/1--stage cool), or HP or PH for heat pump

model (2--stage heat/1--stage cool).

Step 3 — Set Thermostat Configuration

Configuration options allow the installer to configure the
thermostat for a particular installation. These selections are

intended to be made at installation and normally are not modified
by the homeowner. Below is a list of available options followed by

a description of each one.
Option 01 -- Equipment Type
Option 03 -- Fahrenheit or Centigrade operation
Option 04 -- Enable fan (G) ON with heat (W)
Option 10 -- O (reversing valve) On with Heat or Cool (present

on Heat Pump model only)

Option 13 -- Room temperature offset adjustment
Note that not all configuration option numbers are used in this

product.
To Enter The Configuration Mode:
Press and hold FAN button for approximately 10 sec until room
temperature disappears and the display reads “01”. You are now in

configuration mode.
NOTE: If FAN button is pressed again, or if no button is pressed
for 3 minutes, the thermostat will exit configuration mode and
return to normal operation. To re--enter configuration mode, the
FAN button must be pressed and held for 10 sec again.
While in the configuration mode, the temperature display is used to
show both the option number and the selected choice within each

option. Each press of the H/C button alternates between the option
number and the selection within that option. When the

configuration mode is first entered, option 01 is displayed. The up

and down buttons now move between the available option
numbers. Once an option number is selected, press the H/C button

once to display the currently selected choice within that option.
The up and down buttons now move between the available choices

within that option. After the new choice is made, press the H/C

button again to return to the option number display. When finished
with option selections, press FAN button once to exit the

configuration mode.

Option 01 — Equipment Type

Selections: with HP thermostat: HP, AC, PH, or PC

with AC thermostat: AC or PC

Meanings:

PH or PC selects PTAC units (Packaged Terminal Air

Conditioners) which are used in motel rooms and other
rented spaces. When this option is selected, the display

shows only the setpoint, not the room temperature. Also
the compressor timeguard is disabled, allowing the

compressor to turn on immediately when a demand is

established.

HP or PH controls 1 speed heat pump with 1 stage of aux heat.
AC or PC controls 1 speed air conditioner with one stage of heat.
Note that this option allows a HP thermostat to be converted to

control an AC system.

Option 03 — Fahrenheit/Centigrade Selection

This selection operates the thermostat in either Fahrenheit or
Centigrade. Factory default is F.