Table 2 — Electrical Data (Cont)

UNIT
558D

NOMINAL

V-PH-Hz

IFM

TYPE

VOLTAGE

RANGE

COMPR

(each)

OFM

IFM

ELECTRIC HEAT*

POWER SUPPLY

DISCONNECT

SIZE**

Min

Max

RLA

LRA

FLA

FLA

Nominal kW

FLA

MCA

MOCP†

FLA

LRA

060

(5 Ton)

208/230-1-60

Std

187

254

28.8

147

1.4

5.9

—

—

43.3/ 43.3

60/ 60

42/ 42

159/159

4.9/ 6.5

23.5/27.1

43.3/ 43.3

60/ 60

42/ 42

159/159

6.5/ 8.7

31.4/36.3

46.6/ 52.7

60/ 60

43/ 49

159/159

9.8/13.0

46.9/54.2

66.0/ 75.1

70/ 80††

61/ 69

159/159

13.0/17.4

62.8/72.5

85.9/ 98.0

90/100††

79/ 90

159/159

15.8/21.0

75.8/87.5

102.2/116.8

110/125††

94/107

159/159

Alt

8.8

—

—

46.2/ 46.2

60/ 60

45/ 45

162/162

4.9/ 6.5

23.5/27.1

46.2/ 46.2

60/ 60

45/ 45

162/162

6.5/ 8.7

31.4/36.3

49.9/ 55.9

60/ 60

46/ 52

162/162

9.8/13.0

46.9/54.2

69.3/ 78.3

70/ 80††

64/ 72

162/162

13.0/17.4

62.8/72.5

89.2/101.3

90/110††

82/ 93

162/162

15.8/21.0

75.8/87.5

105.5/120.0

110/125††

97/110

162/162

208/230-3-60

Std

187

254

16.3

114

1.4

5.9

—

—

27.7/ 27.7

35/ 35

27/ 27

126/126

4.9/ 6.5

13.6/15.6

27.7/ 27.7

35/ 35

27/ 27

126/126

7.9/10.5

21.9/25.3

34.7/ 38.9

40/ 40

32/ 36

126/126

12.0/16.0

33.4/38.5

49.1/ 55.5

50/ 60

46/ 51

126/126

15.8/21.0

43.8/50.5

62.1/ 70.5

70/ 80††

57/ 65

126/126

19.9/26.5

55.2/63.8

76.4/ 87.1

80/ 90††

70/ 80

126/126

Alt

5.8

—

—

26.8/ 26.8

40/ 40

27/ 27

125/125

4.9/ 6.5

13.6/15.6

26.8/ 26.8

40/ 40

27/ 27

125/125

7.9/10.5

21.9/25.3

35.3/ 39.5

45/ 45

32/ 36

125/125

12.0/16.0

33.4/38.5

49.6/ 56.0

60/ 60

45/ 51

125/125

15.8/21.0

43.8/50.5

62.6/ 71.1

70/ 80††

57/ 65

125/125

19.9/26.5

55.2/63.8

77.0/ 87.6

80/100††

70/ 80

125/125

460-3-60

Std

414

508

7.4

64

0.8

3.2

—

—

13.3

20

13

69

6.0

7.2

13.3

20

13

69

11.5

13.8

21.3

25

20

69

14.0

16.8

25.0

30

23

69

23.0

27.7

38.6

40

36

69

25.5

30.1

41.6

45

38

69

Alt

2.6

—

—

12.7

20

12

70

6.0

7.2

12.7

20

12

70

11.5

13.8

21.0

25

19

70

14.0

16.8

24.8

30

22

70

23.0

27.7

38.3

45

35

70

25.0

30.1

41.3

45

38

70

575-3-60

Std

518

632

6.2

52

0.8

࿣

3.2

࿣

—

—

11.8

15

12

57

Alt

2.6

࿣

—

—

11.2

15

12

59

072

(6 Ton)

208/230-3-60

Std

187

254

23.6

146.0

1.4

5.2

—

—

36.1/ 36.1

45/ 45

35/ 35

191/191

4.9/ 6.5

13.6/15.6

36.1/ 36.1

45/ 45

35/ 35

191/191

7.9/10.5

21.9/25.3

36.1/ 38.1

45/ 45

35/ 35

191/191

12.0/16.0

33.4/38.4

48.2/ 54.6

50/ 60

44/ 50

191/191

15.8/21.0

43.8/50.5

61.2/ 69.6

70/ 70††

56/ 64

191/191

19.9/26.5

55.2/63.8

75.6/ 86.2

80/ 90††

70/ 79

191/191

460-3-60

Std

414

508

10.6

73.0

0.8

2.6

—

—

16.7

20

16

90

6.0

7.2

16.7

20

16

90

11.5

13.8

20.5

25

19

90

14.0

16.8

24.3

25

22

90

23.0

27.8

37.8

40

35

90

25.5

30.7

41.6

45

38

90

575-3-60

Std

518

632

8.5

58.4

0.8

࿣

2.6

࿣

—

—

13.3

20

14

75

IMPORTANT: Optional, alternate evaporator-fan motor and drive are not available for
558D072 units. Contact your local representative for more information about field-
installed motors.

LEGEND

COMPR — Compressor
FLA

— Full Load Amps

HACR

— Heating, Air Conditioning and Refrigeration

IFM

— Indoor (Evaporator) Fan Motor

LRA

— Locked Rotor Amps

MCA

— Minimum Circuit Amps

MOCP

— Maximum Overcurrent Protection

NEC

— National Electrical Code

OFM

— Outdoor (Condenser) Fan Motor

RLA

— Rated Load Amps

*Available for field-installed accessory heaters only. Heater capacity (kW) is based on

heater voltage of 208 v, 240 v or 480 v. If power distribution voltage to unit varies from
rated heater voltage, heater kW will vary accordingly.

†Fuse or HACR circuit breaker.

**Used to determine minimum disconnect per NEC.

††Fusing single-point box provides the required branch circuit protection.

࿣

Ampacities are based on 460 v. MCA and MOCP are based on 575 v.

NOTES:
1. In compliance with NEC requirements for multimotor and combination load equip-

ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than
2%. Use the following formula to determine the percent of voltage imbalance.

% Voltage Imbalance

max voltage deviation from average voltage

= 100 x

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

=

457

NOTE: The 575-v units are Canada only.

Determine maximum deviation from average voltage.
(AB) 457 - 452 = 5 v
(BC) 464 - 457 = 7 v
(AC) 457 - 455 = 2 v

Maximum deviation is 7 v.

Determine percent voltage imbalance.

7

% Voltage Imbalance = 100 x

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allow-
able 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your
local electric utility company immediately.

—11—