Briggs & Stratton 202826GS User Manual

Page 16

Advertising
background image

16

BRIGGSandSTRATTON.COM

Initial Start-up (No Load)

Beforeoperatingthehomegeneratororplacingitinto

service,inspecttheentireinstallationcarefully.
Thenbegintestingthesystemwithoutanyelectricalloads

connected,asfollows:
 1. Setgenerator’smaincircuitbreakertoitsON(closed)

position.

 . Install15Ampfuseincontrolpanel.
 3. Setgenerator’ssystemswitchtoAUTO.
 4. PushMANUAL OVER-RIDEbuttononcontrolpanel.
NOTE:Whenthehomegeneratorisstartedforthevery

firsttime,itwillrequirethatairinthegaseousfuellinesbe

purged.Thismaytakeafewminutes.
 5. DONOTcrankengineformorethan10seconds,then

pausefor10secondstoreduceheatinthestarter.

 6. Repeatprocessuntilenginestarts.
 7. Listenforunusualnoises,vibrationorotherindications

ofabnormaloperation.Checkforoilleakswhileengine

runs.

 8. Letenginewarmupforaboutfiveminutestoallow

internaltemperaturestostabilize.

 9. ConnectanaccurateACvoltmeterandafrequency

metertocheckgeneratoroutputatloadsideofcircuit

breaker.Voltageshouldbe39-6Volts,frequency

shouldbe6.0-6.5Hz.

NOTE:Ifeitherparameterisoutsidetheseranges,perform

theEngineAdjustmentsdescribedbelow.
10. Checkgeneratoroutputbetweenoneofthegenerator

connectionlugsandtheneutrallug,thenbetweenthe

othergeneratorconnectionlugandtheneutrallug.

Inbothcases,voltagereadingshouldbebetween

119-131Volts.

11. PushandholdMANUAL OVER-RIDEbuttononcontrol

panelagainuntilenginestops.

IMPORTANT:DONOTproceeduntilyouarecertainthat

generatorACvoltageandfrequencyarecorrectandwithin

thestatedlimits.Toobtainthepropergeneratorfrequency,

seeEngine Adjustments.

Engine Adjustment

Eachhomegeneratorunitleavesthefactorysetforeither

NGorLPgasoperation.Thereareregionalvariancesinthe

compositionofnaturalgas.Ifthegeneratoroutputvoltage

orfrequencymeasuredduringInitialStart-Up(paragraph#9)

isoutsidethelistedranges,thecombustibilityofthegas

suppliedattheinstallationsitemaybesubstantiallydifferent

fromthefuelusedatthefactory.
Toadjusttheengineforthisdifference,proceedasfollows.
 1. Opentheoildrainandcontrolpanelaccessdoors.
 . Removethefourscrewsthatholdthecircuitbreaker

covertotheairintakeguard.

 3. Connectanaccuratefrequencymetertothelinesideof

thegenerator’smaincircuitbreaker.

 4. Ensurethatthe15Ampfuseisinstalled.
 5. Setthegenerator’smaincircuitbreakerON.
 6. Setthegenerator’ssystemswitchtoAUTO.
 7. PushMANUAL OVER-RIDEbuttononcontrolpanel.

Whentheenginestarts,allowittowarmupforfive

minutes.

Advertising