Troubleshooting, Reparacion de averias, Dépannage – Briggs & Stratton 71013 User Manual

Page 13

Advertising
background image

11

Troubleshooting

Problem

Cause

Correction

Supervised loads (air conditioner, etc.)
are not operating when generator is
supplying power

1.

AC1A-AC2B contacts not operating
correctly.

2.

Too much load on generator.

3.

Current transformer not connected.

4.

Broken current transformer.

5.

Status LED stays lit constantly.

1A. Check AC1A-AC2B contacts for

proper operation.

B. Check control wiring to external

load.

C. Check harness between boards is

properly connected.

D. Check that there is 24 VAC to one of

the terminals.

E. Be sure 5 minute lock out has

elapsed.

F. Be sure air conditioner start time

delay has elapsed.

2.

Decrease load to generator.

3.

Connect current transformer.

4.

Replace current transformer.

5.

Contact an authorized service
center.