Power wiring interconnections, Interconexiones de cableado, Interconnexions du câblage d – Briggs & Stratton 71013 User Manual

Page 7: Warning, Notice

Advertising
background image

5

Power Wiring Interconnections

All wiring must be the proper size, properly supported and
protected by conduit. All wiring should be done per
applicable federal, state and local codes, standards and
regulations.

Complete the following connections between the transfer
switch, power management system and main breaker panel.
Also see the Wiring Decal on page 8.

1. Set generator’s system switch to OFF position.

2. Set generator’s main circuit breaker to OFF (open)

position.

3. Identify loads and their priorities (using list developed

with owner) to be transferred to power management
system in main breaker panel.

4. In main breaker panel, turn selected load circuit

breakers to OFF position.

5. Connect “GND” lug to an approved ground.

NOTE: Assure grounding electrode conductor is connected
and bonded per applicable federal, state and local codes,
standards and regulations.

6. Using installer supplied 300VAC or greater wire and

supplied 1/4” double male, single female lugs, connect
generator 240VAC from transfer switch to relay board
in power management system.

7. Unplug current transformers from control module in

transfer switch.

Ground Lug

To Transfer Switch

Air Conditioner

Relays

Load

Connection

Control
Module

Test

Button

Generator

Connection

Air Conditioner

Connections

Relay Board

To Air Conditioners

Transfer Switch

Connections

Green LED’s

Wireways

• Failure to follow above warning could cause personal injury,

damage and/or malfunction of equipment.

WARNING

Low voltage wire cannot be installed in same
conduit as power voltage wiring.

• Remove all power prior to installing this power management

system. Failure to do so could cause internal damage to the
board when making electrical connections.

• Turn generator to OFF position.

• Turn off utility power to the home standby generator and transfer

switch.

NOTICE

Improper installation can cause damage to the circuit
boards and shorten their life. Installing circuit boards in live
circuits will damage the board and is not a warranty
condition. ALWAYS disconnect ALL sources of power prior
to servicing.