581b036-150 – Bryant 581A/B User Manual

Page 10

Advertising
background image

10

ARI* CAPACITY RATINGS — 581B036-150

LEGEND

*Air-Conditioning & Refrigeration Institute.

†Applies only to units with capacity of 65,000 Btuh or less.

**The IPLV is not applicable to single-compressor units.

NOTES:
1. Rated in accordance with ARI Standard 210/240 (036-120 units) or

360 (150 units) and 270 (036-150 units).

2. Ratings are net values, reflecting the effects of circulating fan heat.

Ratings are based on:
Cooling Standard: 80 F db, 67 wb indoor entering-air temperature
and 95 F db outdoor entering-air temperature.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature
and 80 F db outdoor entering-air temperature.

3. All 581B036-150 units are in compliance with ASHRAE 90.1-1999

Energy Standard for minimum SEER and EER requirements. Refer
to state and local codes or visit the following website: http://sol-
stice.crest.org/efficiency/bcap to determine if compliance with this
standard pertains to a given geographical area of the United States.

4. All 581B036-120 units are Energy Star certified.

HEATING CAPACITIES AND EFFICIENCIES — 581B036-150

208/230-1-60 — SINGLE-STAGE GAS HEAT

LEGEND

AFUE — Annual Fuel Utilization Efficiency.

208/230-1-60 — SINGLE-STAGE GAS HEAT — LOW NOx

LEGEND

AFUE — Annual Fuel Utilization Efficiency.

UNIT
581B

NOMINAL

TONS

COOLING

(Btuh)

TOTAL

kW

SEER†

EER

SOUND RATING

dB

IPLV

036

3

36,000

3.21

13.0

11.20

76

**

048

4

46,000

4.25

13.0

11.05

76

**

060

5

61,000

5.55

13.0

11.00

80

**

072

6

73,000

6.70

11.00

80

**

090

7

1

/

2

90,000

8.18

11.00

82

11.6

102

8

1

/

2

103,000

8.90

11.60

82

12.8

120

10

120,000

10.91

11.00

84

11.4

150

12

1

/

2

138,000

14.40

9.6

86

10.3

EER

Energy Efficiency Ratio

IPLV

Integrated Part-Load Value

SEER — Seasonal Energy Efficiency Ratio

Sizes 036-120

Only

Sizes 150

Only

UNIT
581B

INPUT CAPACITY

OUTPUT CAPACITY

TEMPERATURE

RISE (°F)

MINIMUM HEATING

AIRFLOW (CFM)

EFFICIENCY

AFUE (%)

Steady State (%)

036072

72,000

58,000

25-55

1004

82.8

82.0

036115

115,000

90,000

55-85

1002

80.0

80.0

048072

72,000

58,000

25-55

1004

82.8

82.0

048115

115,000

90,000

35-65

1320

81.0

81.0

048150

150,000

118,000

50-80

1396

80.4

80.0

060072

72,000

58,000

25-55

1004

82.8

82.0

060115

115,000

92,000

35-65

1327

81.0

81.0

060150

150,000

118,000

50-80

1314

80.4

80.0

UNIT
581B

INPUT CAPACITY

OUTPUT CAPACITY

TEMPERATURE

RISE (°F)

MINIMUM HEATING

AIRFLOW (CFM)

EFFICIENCY

AFUE (%)

Steady State (%)

036060N

60,000

50,000

20-50

930

80.2

81.2

036090N

90,000

74,000

30-60

1150

81.0

81.4

048060N

60,000

50,000

20-50

930

80.2

81.2

048090N

90,000

74,000

30-60

1150

81.0

81.4

048120N

120,000

101,000

40-70

1340

80.7

82.4

060060N

60,000

50,000

20-50

930

80.2

81.2

060090N

90,000

74,000

30-60

1150

81.0

81.4

060120N

120,000

101,000

40-70

1340

80.7

82.4

Advertising