134 electrical data (cont) – Bryant 581A/B User Manual

Page 134

Advertising
background image

134

ELECTRICAL DATA (cont)

581B036-150 UNITS

LEGEND

*The values listed in this table do not include power exhaust. See table at right for power

exhaust requirements.

†Used to determine minimum disconnect per NEC.

**Fuse or HACR circuit breaker.

NOTES:

1.

In compliance with NEC requirements for multimotor and combination load equipment
(refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be
fuse or HACR breaker. The UL, Canada units may be fuse or circuit breaker.

2.

Electrical data based on 95 F ambient outdoor-air temperature ± 10% voltage.

3.

Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percent of voltage imbalance.

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

Determine maximum deviation from average voltage.

(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

This amount of phase imbalance is satisfactory as it is below the maximum allowable
2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local
electric utility company immediately.

POWER EXHAUST ELECTRICAL DATA

N/A — Not Available

*Single or three phase.
NOTE: If a single power source is to be used, size wire to include power exhaust MCA
and MOCP.
Check MCA and MOCP when power exhaust is powered through the unit. Determine the
new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 581B060 unit with MCA = 28.9 and MOCP = 35, with
CRPWREXH030A01 power exhaust.
MCA New = 28.9 amps + 1.6 amps = 30.5 amps
If the new MCA does not exceed the published MOCP, then MOCP would not change.
The MOCP in this example is 35 amps and the MCA New is below 35; therefore the
MOCP is acceptable. If “MCA New” is larger than the published MOCP, raise the MOCP
to the next larger size. For separate power, the MOCP for the power exhaust will be
15 amps per NEC.

UNIT SIZE

581B

NOMINAL

V-PH-Hz

IFM TYPE

CONV

OUTLET

VOLTAGE

RANGE

COMPRESSOR (each)

OFM (each)

IFM

FLA

COMBUSTION

FAN MOTOR

POWER SUPPLY*

MINIMUM UNIT

DISCONNECT SIZE†

Min

Max

Qty

RLA

LRA

Qty

FLA

FLA

MCA

MOCP**

FLA

LRA

102

(8

1

/

2

Tons)

208/230-3-60

STD

NO

187

254

2

13.1

105

2

1.4

7.5

0.6

40.2

45

42

276

YES

46.2

50

48

281

HIGH

NO

10.6

43.3

50

46

301

YES

49.3

60

51

305

460-3-60

STD

NO

414

508

2

7.4

55

2

0.7

3.4

0.3

21.5

25

23

143

YES

24.2

30

25

145

HIGH

NO

4.8

22.9

25

24

156

YES

25.6

30

27

158

575-3-60

STD

NO

518

632

2

6.4

44

2

0.6

2.8

0.3

18.2

20

19

115

YES

20.4

25

21

116

HIGH

NO

3.3

18.9

25

20

124

YES

21.1

25

22

126

PH

NO

0.7

4.8

0.3

19.4

25

20

124

YES

21.5

25

22

126

120

(10 Tons)

208/230-3-60

STD

NO

187

254

2

17.6

125

2

1.4

10.6

0.6

53.0

60

56

341

YES

59.0

70

61

345

HIGH

NO

15.0

0.6

57.4

70

61

364

YES

63.4

70

66

369

460-3-60

STD

NO

414

508

2

8.3

62.5

2

0.7

4.8

0.3

24.9

30

26

171

YES

27.6

30

29

173

HIGH

NO

7.4

27.5

30

29

182

YES

30.2

35

32

184

575-3-60

STD

NO

518

632

2

6.3

50

2

0.6

3.3

0.3

19.1

25

20

136

YES

21.3

25

22

138

HIGH

NO

5.6

0.3

21.0

25

23

146

YES

23.1

25

25

148

PH

NO

2

0.7

7.4

0.3

21.2

25

23

146

YES

23.4

25

25

148

150

(12

1

/

2

Tons)

208/230-3-60

STD

NO

187

254

2

19

156

2

1.4

15.0

0.6

60.6

70

64

426

YES

66.6

70

70

431

460-3-60

STD

NO

414

508

2

9

75

2

0.7

7.4

0.3

29.1

35

31

207

YES

31.8

35

33

209

575-3-60

ST

NO

518

632

2

7.4

54

2

0.6

5.6

0.3

23.5

30

25

154

YES

25.6

30

27

156

PH

NO

2

0.7

7.4

0.3

23.7

30

25

154

YES

25.9

30

27

156

CONV

Convenience Outlet

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP

Maximum Overcurrent Protection

NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

PH

Perfect Humidity™ Dehumidification System

RLA

Rated Load Amps

UL

Underwriters’ Laboratories

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

452 + 464 + 455

3

=

1371

3

= 457

% Voltage Imbalance = 100 x

7

457

= 1.53%

POWER EXHAUST

PART NO.

APPLICATION

USAGE

MCA

(230 V)

MCA

(460 V)

MCA

(575 V)

MOCP

(separate

power source

only)

CRPWREXH030A01

036-072*

1.6

N/A 0.64

15

CRPWREXH021A01

036-072

N/A 0.68

N/A

15

CRPWREXH022A01

090-150*

3.4

N/A 1.32

15

CRPWREXH023A01

090-150

N/A 1.4

N/A

15

CRPWREXH028A01

ALL*

1.7

N/A 0.68

15

CRPWREXH029A01

ALL

N/A 0.7

N/A

15

581

B0

36

-15