background image

Pump Rating Chart for

American Models PSD/PSDB/CSD/CSDB/FSD 100

1000 GPM at 150 PSI

Single Stage Pump -10-inch Impeller

Use this chart to select the proper engine to pump ratio. The approximate pump input speed and horsepower requirements shown are for the
underwriter rating*.

Maximum lift at which the pump will do the rating at sea level: ****

With 20 feet of 5-inch suction hose is 15 feet

Maximum elevation at which the pump will do the rating on 10-foot lift: ****

With 20 feet of 5-inch suction hose is 4300 feet.
With 20 feet of 6-inch suction hose is 8000 feet.

10-FOOT LIFT, 20 FEET OF 5-INCH SUCTION HOSE WITH SUCTION TUBE AND HOSE STRAINERS

INPUT DRIVE SHAFT SPEED -- RPM

Rated Capacity

Capacity

US GPM

Pressure

PSIG*

Horsepower

Required

Ratio: 2:37

Ratio: 2.16

Ratio: 1.81

Ratio: 1.59

Ratio: 1.40

1605

1760

2100

2390

2715

Rating*

1000

150

127

Torque >

416

379

314

275

240

1680

1845

2200

2505

2845

Rating”

1000

165

140

Torque>

439

397

330

287

252

1700

1865

2225

2535

2880

Rating*

700

200

132

Torque>

408

372

312

273

241

1845

2025

2415

2750

3125

Rating*

500

250

147

Torque>

418

381

320

281

247

High

Pressure***

200

300

160

1925

2110

2520

2865

3255

*

Engine speed must not exceed manufacturer's maximum no-load governed speed.

**

Gauge pressure does not include lift or suction losses.

*** The pump is capable of the high pressure performance shown; actual obtainable pressure should be checked in advance, and is governed by maximum

engine speed, available horsepower and pump ratio.

**** Maximum lift/elevation listed with direct suction hose pump hookup.

Gross engine power curves represent power without accessories. To obtain net power for pumping, deduct for accessory power losses, and deduct for
elevations above sea level per engine manufacturer's recommendations.

When pump is driven via the front engine crankshaft PTO or transmission PTO, the PTO rating should equal or exceed

pump power requirements.