Installation Instructions

GENERAL

Direct fired heaters discharge combustion by-products with
the heated air in to the area being heated. These include
CO, CO

2

, NO, NO

2

, and Ethylene. These gases can result in

harm to the worker or the plants.

This greenhouse heater has been specifically developed for
very low levels of these combustion by-products. However, it
is necessary to have an exchange of air within the
greenhouse to avoid accumulation of these gases to a
harmful level over an extended period of operating time.

Greenhouses have a natural air leakage factor. This natural
leakage is influenced by the design and physical condition of
the greenhouse as well as wind conditions and other factors.
This natural leakage factor can not be relied upon as being
sufficient to provide the necessary air exchange within the
greenhouse.

Proper

installation

of

the

GreenGro

greenhouse heater must include provision for adequate air
exchange as follows:

Indoor Mounted Heater:

--

An exhaust fan capable of providing at least 300 cfm
of discharge air.

--

An inlet shuttered louver of at least 120 sq. in. area.

--

The inlet shutters must be electromachanically
operated and electrically interlocked with the heater
such that the heater can not operate if the inlet
shutters do not open when heating is required.

--

Refer to Indoor Ventilation Requirements in this
manual.

Outdoor Mounted Heater:

--

An exhaust shuttered louver of at least 64 sq. in.
area.

--

The exhaust shutter must be electromechanically
operated and electrically interlocked with the heater
such that the heater can not operate if the exhaust
shutters do not open when heating is required.

1.

Read all safety precautions and follow L. B. White
recommendations when installing this heater.

If

during the installation or relocating of heater, you
suspect that a part is damaged or defective, call a
qualified service agency for repair or replacement.

2.

Make sure the heater is properly positioned before use
and is hung level. Observe and obey all minimum safe
distances of the heater to the nearest combustible
materials. Minimum safe distances are given on the
heater nameplate and on page 4 of this manual.

3.

The heater may be used either indoors or outdoors.
For heaters intended for outdoor installation, the
heater is to be installed at least 18 inches above the
ground or to a height that would prevent snow
blockage of heater’s air inlet.

Refer to instructions

provided in the optional L.B. White outdoor mounting
and ducting kit, part number 23578.

4. The heater must have the proper gas regulator installed

for the application. A regulator must be connected to
the gas supply so that gas pressure at the inlet to the
gas valve is regulated within the range specified on the
dataplate at all times. Contact your gas supplier, or the
L.B. White Co., Inc. if you have any questions.

5.

The heater’s gas regulator (with pressure relief valve)
should be installed outside of building. Any regulators
inside the buildings must be properly vented to the
outside. Local, state and national codes always apply
to regulator installation. Natural gas regulators with
vent limiting device may be mounted indoors without
venting to outdoors.

6.

All gas pressure regulators must be installed in strict
accordance with the manufacturer’s safety instructions.
These instructions accompany each regulator.

7.

Insure that all accessories that ship within the heater
have been removed from inside of heater and
installed.

This pertains to air diverters, hose,

regulators, etc.

8.

Make certain that a sediment trap is installed at the
gas valve inlet to prevent foreign materials (pipe
compound, pipe chips and scale) from entering the
gas valve. Debris blown into the gas valve may cause
that valve to malfunction resulting in a serious gas
leak that could result in a possible fire or explosion
causing loss of products, building, or even life.

A

properly installed sediment trap will keep foreign
materials from entering the gas valve and protect the
safe functioning of that important safety component.

9.

Any heater connected to a piping system must have an
accessible, approved manual shut off valve installed
within six feet (6 ft.) of the heater it serves.

10.

Check all connections for gas leaks using approved
gas leak detectors. Gas leak testing is performed as
follows:

-- Check all pipe connections, hose connections,

fittings and adapters upstream of the gas
control with approved gas leak detectors.

-- In the event a gas leak is detected, check the

components involved for cleanliness and
proper application of pipe compound before
further tightening.

-- Furthermore tighten the gas connections as

necessary to stop the leak.

-- After all connections are checked and any

leaks are stopped, turn on the main burner.

-- Stand clear while the main burner ignites to

prevent injury caused from hidden leaks that
could cause flashback.

-- With the main burner in operation, check all

connections, hose connections, fittings and
joints as well as the gas control valve inlet and
outlet connections with approved gas leak
detectors.

WARNING

Fire and Explosion Hazard

Do not use open flame (matches, torches, candles, etc.)
in checking for gas leaks.

Use only approved leak detectors.

Failure to follow this warning can lead to fires or
explosions.

Fires or explosions can lead to property damage,
personal injury or loss of life.