INDOOR VENTILATION REQUIREMENTS

This heater requires a properly sized, motorized air inlet
shutter and exhaust fan for indoor installation. These
components, along with specific instructions, are provided in
indoor ventilation kit # 25995.

Air Inlet

Locate the air inlet directly beneath the heater and align it to
the heaters air inlet for combustion air supply. Ensure the
motorized air inlet and the heater’s air inlet are kept free of
any blockages.

The air inlet must be located directly beneath the
heater’s air inlet, and have access to outside fresh air.
See Fig. 4a.

The heater draws its combustion air through holes in its
base. The motorized air inlet must be centered to the
heater’s air inlet. See Fig. 4b.

The motorized air inlet must be no more than 1 ½ ft.
from the back of the heater and properly aligned to the
heater. See Fig. 4c.

The heater should have a minimum clearance of 1 ½ ft.
above the ground. See Fig. 4c.

Refer to Figs. 4a, 4b, and 4c for air inlet placement. If the air

inlet must be installed away from the heater in a location
other than as follows, duct kit part number 26005 must also
be installed to allow supply of combustion air to the heater.

FIG. 4a

Blower Outlet View

FIG. 4b

Underside View

FIG. 4c

Side View

1 1/2 FT MAX.

MOTORIZED AIR INLET

ALIGNED TO AIR INLET

IN BASE OF HEATER

HEATER AIR INLET

AIR INLET

TRANSITION

CENTERED

INTERIOR EXTERIOR

1 1/2 FT MAX.

OUTSIDE

AIR SOURCE

1 1/2 FT

MAX.

TOP OF AIR INLET

TRANSITION ALIGNED

WITH BASE OF HEATER

OUTSIDE

AIR SOURCE

AIR

DISCHARGE

1 1/2 FT

MIN.