Follow these start-up instruction steps for initial start-up

before building repopulation. For normal start-up, simply

turn the thermostatic head above room temperature.

1. Open all gas supply valves to the heater(s) and check

for gas leaks at all connections using approved lead

detectors.

2. Adjust the thermostatic head, located on either the

zone control panel, or for individually controlled

heaters, directly on the heater, to its maximum

temperature setting. See Fig. 7.

FIG. 7

3. Fully depress the button on the safety control valve

while applying flame to the inner cone point. Keep

the button fully depressed for about 30 seconds until

the inner cone stays lit. Allow outer combustion cone

to heat up completely.

4. Adjust the temperature by decreasing the setpoint on

the thermostatic head to the desired temperature.

The heater will cycle from low heat to high heat

based upon thermostatic head set point.

FIG. 8

INDICATOR

100ºF

38ºC

THERMOSTATIC
HEAD

1111

Start-Up Instructions

To reduce temperature, simply turn down the thermostatic

control on the zone panel or on the individual heater.

To shut down the heaters for maintenance, cleaning or

service:

1.

Shut off all gas supply valves to the heaters.

2.

Allow heaters to burn off fuel gas remaining in the

gas supply line.

3.

Turn down the thermostatic head to minimum

setting.

Shut-Down Instructions

PILOT BUTTON

PILOT CONTROL VALVE

BUTTON

SAFETY CONTROL VALVE

W

WAARRNNIINNGG

FFiirree oorr EExxpplloossiioonn HHaazzaarrdd

Do not force the safety gas control valve button.

Use only your hand to depress the gas control button.

Never use any tools.

If the button will not depress by normal hand

pressure, the control should be replaced by a

qualified service person.

Force or attempted repair may result in fire or

explosion, causing property damage, severe injury, or

death.