SECTION 6 - TROUBLESHOOTING

3121136

– JLG Lift –

6-19

Code 19 - Alarm - Disconnected

Check For These Obvious Conditions First:

• Damaged wiring in the alarm wiring harness or a damaged alarm.

• Activate a function to check if alarm beeps.

Code 20 - Beacon - Short Circuit

Check For These Obvious Conditions First:

• Damaged wiring in the beacon wiring harness or a damaged beacon unit.

Table 6-22. Code 19 - Alarm - Disconnected

STEP

ACTION

SPEC

YES

NO

1.

Check voltage at the P1 connector on the Ground Control Module
between pin-13 and pin-6. Is reading within specification?

2 - 4V DC

Replace Ground

Control Module

Go to Step 2

2.

Remove the wire terminals at the alarm, check continuity of each of
the wires from pins 13 and 6 on the P1 connector to the alarm end.

Replace the

Alarm

Repair or

Replace Wiring

Table 6-23. Code 20 - Beacon - Short Circuit

STEP

ACTION

SPEC

YES

NO

1.

At the Ground Control Module, P1 connector, check the voltage
across pins-12 and 5 to the beacon. Is reading within specification?

0 - 2V DC

Go to Step 2

Replace Ground

Control Module

2.

Remove the wire terminals at the beacon, check continuity of each
of the wires from pins 12 and 5 on the P1 connector to the beacon
end.

Replace the

Beacon

Repair or

Replace Wiring