SECTION 6 - TROUBLESHOOTING
6-28
– JLG Lift –
3121136
Codes 41 thru 46 - OSS - Sensor 1 through 6 - Fault Condition
Check For These Obvious Conditions First:
• Is there an obstruction under the sensor showing the fault?
• Is the faulted sensor mounted properly and securely to the platform base frame?
12.
At the Ground Control Module (P-4 connector) check voltage
between pin-8 and pin-2, place positive (+) lead on pin-8.
24V (DC)
Repair or
Replace, Junc-
tion Box to
Ground Control
Module
Wire Harness
Replace Ground
Control Module
Table 6-36. Codes 41 thru 46 - OSS - Sensor 1 through 6 - Fault Condition
STEP
ACTION
SPEC
YES
NO
1.
Is machine equipped with an OSS system?
—
Got to Step 4
Go to Step 2
2.
At the Ground Control Module, enter programming mode and view if
OSS is enabled. Is OSS enabled?
X = No
Go to Step 3
Replace Ground
Control Module
3.
In Service Level Programming mode, Disable Obstruction Senor
System.
X=No
—
Go to Step 4
4.
Replace the sensor showing the fault. Does this correct the prob-
lem.
—
Done
Go to Step 5
5.
Replace the complete OSS system, module and sensors.
—
—
—
Table 6-35. Code 40 - OSS - No Communication with Ground Control Module (Continued)