SECTION 6 - TROUBLESHOOTING

6-32

– JLG Lift –

3121136

6.9

MAIN POWER CIRCUIT TROUBLESHOOTING

Machine Will Not Power Up

Check For These Obvious Conditions First:

• Battery voltage is 24 volts. (Sufficient Charge in Batteries to Operate Machine)

• Positive (+) and negative (–) battery cable connections clean and tight at both the Batteries and the Ground Control Mod-

ule lugs.

• Main Power Selector Switch (key) positioned to either Platform or Ground Control Mode.

• Emergency stop buttons on both the Ground Control Module and the Platform Control Console in the RESET position

(out).

Table 6-40. Machine Will Not Power UP.

STEP

ACTION

SPEC

YES

NO

1.

Check for 24V DC at the positive (+) and negative (–) main power
cable connections on the Ground Control Module.

24V DC

Go to Step 2

Replace the 175

Amp Inline Fuse

on the Positive

power cable

2.

Check continuity of the Emergency Stop wires running to the Plat-
form Control Console, pins-10 and 1 on the P4 connector at the
Ground Control Module.

Replace the

Ground Control

Module

Go to Step 3

3.

Remove the 9-pin Platform Control Console connector at the Plat-
form Junction Box and check continuity between pins-1 and 2 to the
Emergency Stop Switch in the Platform Control Console cable.

Go to Step 4

Replace the

Platform Control

Console

4.

Check continuity of the wires running from the P4 connector on
Ground Control Module to the Platform Junction Box;
P4 connector, Pin-1 to Junction Box Pin-2 and
P4 connector, Pin-10 to Junction Box Pin-1

Replace Platform

Control Console

Repair or Replace

Wiring