• Trouble Shooting

Use the following information to troubleshoot the malfunctioning sensor. If

the remedies are unsuccessful, ask APG for repair or replacement.

Problem

Liquid exceeds the actuation level, but switch does not activate

Possible Causes

Remedies

SG is larger than 0.85

Choose another technique

Miswiring Wire

correctly

Set for improper fl oat travel-stop Adjust position according to “Assembly”
Liquid immerse in fl oat

Replace the switch

Aff ected by deposit

Clean the switch

Microswitch is damaged

Replace the microswitch

Problem

Liquid does not exceed the actuation level, but switch activate

Possible Causes

Remedies

Miswiring Wire

correctly

Set for improper fl oat travel-stop Adjust position according to “Assembly”
Aff ected by deposit

Clean the switch

Microswitch is damaged

Replace the microswitch