APG RCU-7000 user manual User Manual

Page 7

Advertising
background image

Rev. A1, 4/07

RCU-7000 Series

7

Automation Products Group, Inc.

APG...Providing tailored solutions for measurement applications

Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]

• Operating Characteristics of Relay Units

Table 1 Relay Actuation
RCU-7000 (Standard)

Select Switch Mode

H. ON side

L. ON side

Operating resistance (between E0 and E2)
4 Ký or less

energize

de-energize

Reset resistance (between E0 and E2)
15 Ký or more

de-energize

energize

RCU-7100 (High Sensitivity) Select Switch Mode

H. ON side

L. ON side

Operating resistance (between EO and E2)
50 Ký or less

energize

de-energize

Reset resistances (between E0 and E2)
100 Ký or more

de-energize energize

Table 2 Relay Actuation of Latch
RCU-7000 (Standard)

Operating/Reset Resistance

Select Switch Mode

Between E0 and E1

Between E0 and E2

H. ON side

L. ON side

1

15 Ký or more

15 Ký or more

de-energize energize

2

4 Ký or less

15 Ký or more

de-energize energize

3

4 Ký or less

4 Ký or less

energize

de-energize

4

4 Ký or less

15 Ký or more

energize

de-energize

5

15 Ký or more

15 Ký or more

de-energize energize

RCU-7000 (High Sensitivity)

Operating/Reset Resistance

Select Switch Mode

Between E0 and E1

Between E0 and E2

H. ON side

L. ON side

1

100 Ký or more

100 Ký or more

de-energize energize

2

50 Ký or less

100 Ký or more

de-energize energize

3

50 Ký or less

50 Ký or less

energize

de-energize

4

50 Ký or less

100 Ký or more

energize

de-energize

5

100 Ký or more

100 Ký or more

de-energize energize

Advertising