Chapter 2 - Connections


This chapter will cover the connections required for the

485SDD16. There are three sets of connections: digital I/O, serial
port, and power supply. Do not make any connections to the
485SDD16 until you have read this chapter.


Digital I/O Connections

Connections to the I/O lines are made through the DB25S

(female) I/O port connector. Refer to Table 2.1. See Chapter 5 for
I/O interfacing examples.
Digital Inputs

The digital input lines are CMOS/TTL compatible and can handle

voltages from 0Vdc to +5Vdc.
Digital Outputs

The digital output lines have a maximum voltage of +5Vdc and

are CMOS compatible.
Ground

This pin should be connected to the external digital devices

ground.


Table 2.1 - 485SDD16 I/O Port Pinout

DB-25S

Pin #

Function

DB-25S

Pin #

Function

1

No connection

14

I/O #15

2

No connection

15

I/O #14

3

No connection

16

I/O #13

4

No connection

17

I/O #12

5

No connection

18

I/O #11

6

No connection

19

I/O #10

7 Ground

20 No

connection

8

+12Vdc Input

21

I/O #9

9 I/O

#0

22 I/O

#8

10 I/O

#1

23 I/O

#7

11 I/O

#2

24 I/O

#6

12 I/O

#3

25 I/O

#5

13 I/O

#4

6 485SDD16-1005

Manual

B&B Electronics -- 707 Dayton Road -- Ottawa, IL 61350

PH (815) 433-5100 -- FAX (815) 433-5104

Serial Port Connections

In order to communicate to the 485SDD16 module it must be

connected to an RS-422/RS-485 serial port. The 485SDD16 will
work on a 2-wire or 4-wire RS-485 multi-node network. Refer to
B&B Electronics’ free RS-422/485 Application Note for more
information. The unit automatically detects baud rates from 1200 to
9600. A data format of 8 data bits, 1 stop bit and no parity is used.
Connections are made using terminal blocks. Table 2.2 shows the
terminal blocks and their functions.

A typical 2-wire RS-485 connection is shown in Figure 2.3 and a

typical RS-422 (or RS-485 4-wire) connection is shown in Figure
2.4. Note that the 485SDD16 data line labels use “A” and “B”
designators (per EIA RS-485 Specification). However, some RS-485
equipment uses “+” and “-“ as designators. In almost all cases, the
“A” line is the equivalent of the “-“ line and the “B” is the equivalent of
the “+” line. With an RS-485/422 system there are other factors that
require consideration, such as termination and turn-around delay.
For more information refer to B&B Electronics’ free RS-422/485
Application Note.

Table 2.2 - RS-485 Terminal Block Connections

TB

Label

Signal

Signal

Direction at

485SDD16


Notes

FR

GND

Frame
Ground

-

Connection for frame ground.

TD(A) Transmit

Data (A)

Output

Connection is required. [Loop to
RD(A) for 2-wire hookup]

TD(B) Transmit

Data (B)

Output

Connection is required. [Loop to
RD(B) for 2-wire hookup]

RD(A) Receive

Data (A)

Input

Connection is required. [Loop to
TD(A) for 2-wire hookup]

RD(B) Receive

Data (B)

Input

Connection is required. [Loop to
TD(B) for 2-wire hookup]

+12V +12

Vdc

Power

Input Connection

is

required.

GND

Ground

-

Connection for Signal GND and
Power Supply GND.