Det-Tronics STB Series Sensor Termination Box and Separation Kit User Manual

Page 3

Advertising
background image

3.1

95-8655

3

cERTIFIcATIoN—

FM:

Class I, Div. 1, Groups B, C & D (T6)

Class I, Div. 2, Groups A, B, C & D (T4)

Class II, Div. 1, Groups E, F, & G (T6)

Class II, Div. 2, Groups F, & G

Class III

Tamb = –40°C to +75°C

Enclosure NEMA/Type 4X.

CSA:

Class I, Div. 1, Groups B, C & D

Class I, Div. 2, Groups A, B, C & D (T4A)

Class II, Div. 1, Groups E, F, & G

Class II, Div. 2, Groups F, & G

Class III

Tamb = –40°C to +75°C

Enclosure NEMA/Type 4X.

ATEX:

0539

FM

APPROVED

®

II 2 G

Ex d IIC T6-T4 Gb

EN 60079-29-1

DEMKO 02 ATEX 131324X

T6 (Tamb –55°C to +60°C)

T5 (Tamb –55°C to +75°C)

T4 (Tamb –55°C to +125°C)

IP66.
EN Standards: EN 50270: 2006

EN 60079-0: 2009

EN 60079-1: 2007

EN 60529: 1991+A1: 2000

EN 60079-29-1: 2007.

IECEx:

IECEx ULD 10.0007X

Ex d IIC T6-T4 Gb

T6 (Tamb –55°C to +60°C)

T5 (Tamb –55°C to +75°C)

T4 (Tamb –55°C to +125°C)

IP66.
IEC Standards: IEC 60079-0: 2007

IEC 60079-1: 2007

IEC 60529, 2.1.ed.+Corr. 1:2003+2:2007.

INMETRO:

CEPEL 12.2118

Ex d IIC T4-T6 Gb IP66

T6 (Tamb –55°C to +60°C)

T5 (Tamb –55°C to +75°C)

T4 (Tamb –55°C to +125°C)

IP66.

performance Testing to EN60079-29-1

The measuring function of the Sensor Termination Box,

STB Series, according to Annex II paragraph 1.5.5,

1.5.6 and 1.5.7 of the Directive 94/9/EC, is covered in

this EC-type Examination Certificate in the following

configurations:
1. Controller Model EQ3XXX with EQ22XXDCUEX and

STB and CGS (tested as a gas detection system with

methane applied to the CGS).

2.

STB Termination Box and PIR9400 Infrared

Hydrocarbon Gas Detector (tested with methane

applied to the PIR9400).

3. STB Termination Box and PIRDUCT (tested with

methane applied to the PIRDUCT).

4. R8471 Gas Controller with STB and CGS (tested as a

gas detection system with methane applied to the CGS).

note

All applied gas detection equipment must
be AteX certified to en60079-29-1 and
the configuration must comply with the gas
performance parameters stated in the Installation
Manual.

Special conditions for Safe use (X):

The Sensor Termination Box model STB has an ambient

temperature rating for performance of –55°C to +75°C.

WARNING

Always ensure that the detector/termination
box hazardous (classified) location ratings are
applicable for the intended use.
Do not open the box when an explosive gas
atmosphere may be present.

Installation Instructions
The field wiring connections in the terminal compartment

are IECEx certified and accept wiring diameters from

14 AWG–22 AWG or 2.5 mm

2

–0.33 mm

2

.

The cable entry devices shall be certified in type of

explosion protection flameproof enclosure “d” for use

with the terminal compartment in type of explosion

protection flameproof enclosure “d”. They shall be IP66

rated, suitable for the conditions of use and correctly

installed.
Unused entries shall be closed with suitable certified

blanking elements.
The metal housing for the Model STB must be electrically

connected to earth ground.
For ambient temperatures below –10°C and above

+60°C use field wiring suitable for both minimum and

maximum ambient temperatures.

FM

APPROVED

®

FM

APPROVED

®

FM

APPROVED

®

note

All cable entry devices and blanking elements
shall be Brazil certifiied in the type of explosion
protection, flameproof enclosure ‘d’, suitable for
the conditions of use and correctly installed, with
an ingress protection rating of IP66. A screw or
cover lock is provided for a secondary means of
fastening the cover.