Det-Tronics X9800 IR Flame Detector with Pulse Output User Manual

Page 26

Advertising
background image

95-8555

5.1

24

FM approval Description and performance Report – Continued

FIELD OF VIEw

Very High Sensitivity, Quick Fire Off

Fuel

Size

Distance

feet (m)

Horizontal

(degrees)

Typical Horiz. Response

Time (seconds)

Vertical

(degrees)

Typical Vert. Response

Time (seconds)

n-Heptane

1 x 1 foot

42.5

(13)

+45

–45

12

14

+45

–30

10

16

Methane

32 inch plume

30

(9.1)

+45

–45

7

4

+45

–30

6

4

High Sensitivity, TDSa On, Quick Fire Off

Fuel

Size

Distance

feet (m)

Horizontal

(degrees)

Typical Horiz. Response

Time (seconds)

Vertical

(degrees)

Typical Vert. Response

Time (seconds)

n-Heptane

1 x 1 foot

25

(7.6)

+45

–45

7

7

+45

–30

6

5

Methane

32 inch plume

17.5

(5.3)

+45

–45

6

3

+45

–30

4

4

High Sensitivity, TDSa On, Quick Fire On

Fuel

Size

Distance

feet (m)

Horizontal

(degrees)

Typical Horiz. Response

Time (seconds)

Vertical

(degrees)

Typical Vert. Response

Time (seconds)

Black

Powder

40 Grams

5

(1.5)

+45

–45

0.04

0.03

+45

–30

0.04

0.04

FaLSE aLaRM IMMUNITy

High Sensitivity, TDSa On, Quick Fire Off

False alarm Souce

Distance feet

(m)

Modulated Response

Unmodulated Response

Sunlight, direct, reflected

—

No alarm

No alarm

Vibration

NA

No alarm

No alarm

Arc welding

15 (4.6)

No alarm

No alarm

70 w sodium vapor lamp

3 (0.9)

No alarm

No alarm

250 w mercury vapor lamp

3 (0.9)

No alarm

No alarm

300 w incandescent lamp

3 (0.9)

No alarm

No alarm

500 w shielded quartz halogen lamp

3 (0.9)

No alarm

No alarm

1500 w electric radiant heater

10 (3)

No alarm

No alarm

Two 34 w fluorescent lamps

3 (0.9)

No alarm

No alarm

Advertising