9.2
FM Approval and performance Report – Continued
RESpONSE ChARACTERISTICS
very high Sensitivity
Fuel
Size/Flow Rate
Distance
feet (m)
Average Response
Time (seconds)**
Hydrogen
30 inch plume/100 SLPM*
100 (30.5)
3
Methanol
1 x 1 foot
70 (21.3)
5
* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).
** Add 2 seconds for EQP model.
high Sensitivity
Fuel
Size/Flow Rate
Distance
feet (m)
Average Response
Time (seconds)**
Hydrogen
30 inch plume/100 SLPM*
75 (22.9)
3
Methanol
1 x 1 foot
52.5 (16.0)
2
* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).
** Add 2 seconds for EQP model.
Medium Sensitivity
Fuel
Size/Flow Rate
Distance
feet (m)
Average Response
Time (seconds)**
Hydrogen
30 inch plume/100 SLPM*
50 (15.2)
4
Methanol
1 x 1 foot
35 (10.7)
4
* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).
** Add 2 seconds for EQP model.
Low Sensitivity
Fuel
Size/Flow Rate
Distance
feet (m)
Average Response
Time (seconds)**
Hydrogen
30 inch plume / 100 SLPM*
25 (7.6)
3
Methanol
1 x 1 foot
17.5 (5.3)
3
* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).
** Add 2 seconds for EQP model.