Det-Tronics X2200 UV Flame Detector with Pulse Output User Manual
Page 25

23
95-8552
5.3
FM Approval and performance Report – Continued
RESpONSE ChARACTERISTICS IN ThE pRESENCE OF FALSE ALARM SOURCES
very high Sensitivity (Standard Mode)
FALSE ALARM IMMUNITY
very high Sensitivity (Standard Mode)
False Alarm Source
Distance
feet (m)
Fire Source
Distance
feet (m)
Typical
Response Time
(seconds)
Sunlight, direct, modulated, reflected
—
6-inch propane
10 (3)
< 30
6 kw heater, modulated & unmodulated
10 (3)
1 x 1 foot n-Heptane
75 (22.9)
1
250 w vapor lamp, modulated & unmodulated
3 (0.9)
1 x 1 foot n-Heptane
75 (22.9)
1
300 w incandescent lamp, modulated & unmodulated
3 (0.9)
1 x 1 foot n-Heptane
75 (22.9)
1
1500 w electric radiant heater, modulated & unmodulated
10 (3)
1 x 1 foot n-Heptane
75 (22.9)
1
2-34 w fluorescent lamps, modulated & unmodulated
3 (0.9)
1 x 1 foot n-Heptane
75 (22.9)
1
False Alarm Source
Distance feet (m)
Modulated Response
UnmodulatedResponse
Sunlight, direct, reflected
—
No Alarm
No Alarm
Vibration
N/A
No Alarm
No Alarm
6 kw heater
3 (0.9)
No Alarm
No Alarm
250 w vapor lamp
3 (0.9)
No Alarm
No Alarm
300 w incandescent lamp
3 (0.9)
No Alarm
No Alarm
1500 w electric radiant heater
3 (0.9)
No Alarm
No Alarm
2-34 w fluorescent lamps
3 (0.9)
No Alarm
No Alarm