Appendix f – Det-Tronics PM-5MPX Dual Spectrum IR User Manual
Page 16

14
95-8562
4.1
APPENDIX F
p
SS-
mp
TES
T
l
A
mp
f
igur
e
f
1—
pss
-mp
t
est
lamp
LAMP
REPLACEMENT
REPLACE
XENON
LAMP
MODULE
WITH
PN
18801
(UNDER
WA
TER
KINETICS).
W
ARNING
THIS
UNIT
IS
NOT
RA
TED
FOR
USE
IN
HAZARDOUS
(CLASSIFIED)
LOCA
TIONS
.
CAUTION A
FULL
SYSTEM TEST
RESUL
TS
IN
AN
ALARM
OUTPUT
. THIS
WILL
RESUL
T
IN THE
AUT
OMA
TIC
SUPPRESSION
SYSTEM
BEING
ACTI
VA
TED
IF
IT
IS
NOT
DISABLED
PRIOR
TO
TESTING.
OPERA
TION
TURN
ON
PSS-MP
, WA
IT
15
SECONDS.
TO
CAUSE
AN
ALARM,
HOLD
PSS-MP
SO THA
T
THE
INFRARED
FIL
TER
LENS
IS
LESS THAN
1
INCH
FROM THE
FRONT
OF THE
FLAME
DETECT
OR
TO
BE TESTED.
IT
CAN T
AKE
SEVERAL
SECONDS
FOR THE
DETECT
OR
TO
ALARM.
NOTE FOR
VALID TEST
RESUL
TS, THE TEST
LAMP
AND THE
SENSOR
UNDER TEST
MUST
BE
AT
APPROXIMA
TEL
Y
THE
SAME TEMPERA
TURE.
BA
TTER
Y
REPLACEMENT
THE TEST
LAMP
REQUIRES
6
ALKALINE
C-SIZE
BA
TTERIES.
W
ARNING
CHANGE
BA
TTER
Y
IN
NON-HAZARDOUS
LOCA
TION
ONL
Y.
ON
OFF
INFRARED BEAM
INFRARED FILTER LENS
8 5/8
2 3/8
+
+
+
+
+
+
C
C
CC
C