Automatic optical integrity (oi), Eagle quantum premier devices – Det-Tronics S3 Graphics User Manual

Page 151

Advertising
background image

12-36

EAGLE QUANTUM PREMIER DEVICES

Version 6.0

EAGLE QUANTUM PREMIER DEVICES

Sensor Sensitivity Adjustments

Both the UV and IR sensors have individually adjustable

sensitivity selections. These settings combined with the

signal processing and arc rejection selections will effect how

the detector responds to different types of fires. For details

on the impact of these settings on a variety of common fuels,

refer to the UVIR X5200 instruction manual 95-8546.

Automatic Optical Integrity (Oi)

The UVIR X5200 includes the Automatic Optical Integrity

(Oi) feature — a calibrated performance test that is

automatically performed once per minute to verify complete

detector operation capabilities.

No testing with an external test lamp is required. The

detector automatically performs the same test that a

maintenance person with a test lamp would perform

—once every minute, 60 times per hour. However, a

successful automatic Oi test does not produce an alarm

condition.

The UVIR X5200 signals a fault condition when less than

half of the detection range remains. This is indicated by

the Fault relay and is evident by the yellow color of the

LED on the face of the detector.

The Oi feature is set to automatic as a factory default but

can be deselected for “manual only” operation. Manual

Oi tests can be initiated via the detectors point display in

the S

3

software.

Oi Test Frequency

The default Oi test frequency is once a minute but can be adjusted to any whole minute increment up to a

maximum of ten minutes.

Oi Test Fault

The detector automatically conducts Oi tests to check the integrity of the optical sensing systems. Three

consecutive failed Oi tests will generate a fault condition, which will be indicated by the LED on the face of the

detector turning yellow. The EQP Controller and S

3

software will also annunciate this fault.

In certain environmental conditions like very heavy rain, Oi test failures can occur even though the hardware is

not faulty. To compensate for this the number of failed Oi tests required to generate the fault can be adjusted

upward to a maximum of 30.

X5200 • AUTOMATIC Oi