Det-Tronics PSS-LC Test Lamp for PM-6 Series Detectors User Manual

Tronics, Instructions test lamp pss-ml

Advertising
background image

APPLICATION

The PSS-ML Test Lamp is a compact, battery operated
source of IR radiation for periodic testing of PM-5MP+
Series Flame Detectors. The PSS-ML simulates a fire
by producing a beam of IR radiation with the same
wavelength as the response range of the PM-5MP+,
thereby enabling the operator to verify proper opera-
tion without the need for an open flame. The device is
suitable for use in hazardous (classified) areas.

INSTALLING BATTERIES

CAUTION

Change batteries only in a safe (non-hazardous)
location.

1.

Unscrew the bezel and remove the reflector lamp.

2.

Insert two size “AAA” alkaline batteries as shown
in Figure 1. Observe correct polarity.

3.

Inspect the O-ring to be sure that it is in good
condition, then insert the reflector lamp into the
bezel and install the bezel on the case (turn
clockwise).

ON/OFF

To turn the light on, turn the bezel clockwise until the
light comes on. To turn the light off, turn the bezel
counter-clockwise at least one and a half turns.

TEST PROCEDURE

WARNING

A full system test results in an alarm output. This
will result in the suppression system being acti-
vated if it is not disabled prior to testing.

1.

Suppression System.

Disable the suppression

system if its activation is not desired during this
test.

2.

Operation of PSS-ML Test Lamp.

Turn on the

PSS-ML and wait at least 15 seconds. Direct the
beam into the front of the detector as shown in
Figure 2. Hold the PSS-ML so that the bezel is
less than 1 inch from the front of the flame detec-
tor and move it from side to side to expose both
sensors and to create a “flicker” effect.

INSTRUCTIONS

Test Lamp

PSS-ML

©

Detector Electronics Corporation 2002

3/02

95-8536

DET

-

TRONICS

®

ALKALINE

BATTERY

ALKALINE

BATTERY

BEZEL

REFELCTOR LAMP

AAA ALKALINE BATTERIES (2)

O-RING

CASE AND KEY RING

CLIP

A2110

Figure 1—PSS-ML Test Lamp