Installation instructions, Important, Tdx50 series – ERICO TDX50 Series User Manual

Page 3

Advertising
background image

Installation Instructions

TDX50 Series

34600 Solon Road

Solon, Ohio 44139

(440) 248-0100

www.erico.com

IMPORTANT

WARNING. Several “Delta” and “No-neutral” power systems exist and are often confused.
Failure to correctly identify and use the correct SPD may cause an electrical shock or burn hazard.

Three Phase
Grounded Delta
3Ø 3W+G

("Grounded B Phase")

DESCRIPTION

CONFIGURATION

TYPICAL VOLTAGE

SPD

L1

N

L2

G

Single Phase
(Split)
1Ø 3W+G

120V
120V

120/240V

L-N
L-G

L-L 240V

120/240V TDX50 120/240

L1

N

L2

L3

G

Three Phase Wye
3Ø Wye 4W+G

120V 277V 347V
120V 277V 347V

120/208V 277/480V 347/600V

L-N
L-G

L-L 208V 480V 600V

120/208V TDX50 120/208
277/480V TDX50 277/480
347/600 TDX50 347/600

L1

L2

L3

G

Three Phase Wye
3Ø Wye 3W+G
(No Neutral)

208V 480V 600V

120V 277V 347V

208V 480V 600V

L-L
L-G

208V TDX50 120/208
480V TDX50 277/480
600V TDX50 347/600

(1)

(1)

(1)

240V 480V

0V 0V

240V 480V

L1-G
L2-G
L3-G

L-L 240V 480V

240V 480V

Three Phase
Ungrounded Delta
3Ø 3W+G

0- 240V 0-480V

240V 480V

L-G

L-L 240V 480V

Three Phase
High Leg Delta
3Ø 4W+G

208V

120V

120V

240V

L1-N
L2-N
L3-N

L-L 240V

Use TDX150

or TDX100 Series

Use TDX150

or TDX100 Series

(1)

Cap or insulate neutral

L1

N

G

Single Phase
1Ø 2W+G

120V 240V
120V 240V

120V 240V

L-N
L-G

120V TDX50 120
240V TDX50 240