ERICO 3000 ERITECH SYSTEM User Manual
Page 10

INSTALLATION, OPERATION AND MAINTENANCE MANUAL
8
www.erico.com
t
Is terminated as required. If the
downconductor has been pretermin-
ated before shipment, check that
the termination is still intact and in
good order. See note on Page 14 on
removing protective covers.
t
If the Upper Termination Kit has been
supplied separately, check that the
Cold-Shrink tube in the kit is in good
order, has no tears or cuts and has
not collapsed.
This information along with down-
conductor lengths and quantities (if
more than one length on the one
drum), will be printed on a label on the
side of the Cable Drum(s).
Before installation, in particular, check the
following:
Terminal(s)
t
ERITECH
®
DYNASPHERE terminals have
not been dented in any way.
t
The correct finial tip has been installed,
based on the overall height of the air
terminal above ground.
ERITECH
®
ERICORE Downconductor(s)
t
The cable drum (if supplied) is in a
serviceable condition.
t
Correct length(s)
t
That there is no obvious damage to the
cable.
Checking Lightning Protection Components
on Receipt