General lockout/tagout procedures, Maximum current input – ETC Unison ERn Wall-mount Control Enclosure User Manual

Page 11

Advertising
background image

1

Prepare for Installation

7

General Lockout/Tagout Procedures:

•

Notify all affected employees that a lockout/tagout procedure is ready to begin.

•

Turn off the equipment at the control panel.

•

Turn off or pull the main disconnect. Be sure all stored energy is released or restrained.

•

Check all locks and tags for defects.

•

Attach your safety lock or tag on the energy isolating device.

•

Try to restart the equipment at the control panel to ensure that it is secured.

•

Check the machine for possible residual pressures, particularly for hydraulic systems.

•

Complete the repair or servicing work.

•

Remove the safety lock and adapter.

•

Let others know that the equipment is back in service.

Maximum Current Input

The ERn enclosure draws a maximum current of 3 amps when fully populated. the

maximum allowable protection device rating is:

•

20A at 120 VAC

•

15A at 230/240 VAC