CEM3 Sensor Rack Retrofit Manual

Step 4:

Center the provided 4 1/2” x 1/2” dia. heat shrink tubing over

the power harness connectors (leaving at least 1 1/4” past

each connector). Be sure to keep the green ground wire for

the new harness out of the heat shrink as you will need to

run this ground to a different location.

Step 5:

Contract the heat shrink using a heat gun.

Step 6:

Tuck the power harness connection bundle between the bus

bar and the rack wall.

Step 7:

Route the green ground wire behind the bus bar, between

the rack wall and existing wires and land it at an open

terminal on any existing grounding bus in the rack using a square drive of phillips

screwdriver.

Step 8:

Use a wire tie to secure the ground wire to the wire bundle as it protrudes from

the heat shrink.

Connect Dimmer Output Cables to New Backplane

Step 1:

Identify the different dimmer output ribbon cable transition cards. An SR6 and

SR12 will only have a single “lower” card.

N o t e :

There are two different types. An “upper” card and a “lower” card. The PCB card

is marked for both types and which side is up when installed.

1-1/4"

1-1/4"

Min.

Min.

1-1/4"

Min.

4 1/2"

4 1/2"

4 1/2"

Secure ground

with wire tie

1

3

4

2

This is an “Upper”

transition board

(7150B5007)

This is a “Lower”

transition board

(7150B5006)