Case A
You have an MGB with a version number of V 2.35.4 and a GSD file with a version
number of ..._110026-20110725 or older. Or you have an MGB with a version num-
ber of V 2.35.4 and a GSD file with a version number from ..._110026-20110815.
The guard locking solenoid is controlled if
Ì
bit O16 OR bit SO1 = 1
Truth table:
PROFINET bit
PROFIsafe bit
Guard locking with
O16
SO1
MGB-L1...
MGB-L2...
0
0
active
inactive
0
1
inactive
active
1
0
inactive
active
1
1
inactive
active
What must be observed?
The guard locking can be controlled from the unsafe control area. The combination
with the more up-to-date GSD file allows a parameter to specify which bits are to
be used for control. However, the device does not support this function. In other
words, the setting in your configuration software remains ineffective.