40
—
SWITCH CLOSES
ON BP,SP,E
EMC
EAS
*
OPEN
ON BP
OPEN ON E
CLOSED ON BP
OPEN
ON SD
CLOSED ON
BP,SP,E
COMPRESSOR WIRING
See Legend on page 2.
*Included in power exhaust accessory.
NOTE: All switches are field supplied.
OPERATING MODES
Fig. 21 — Smoke Control/Fire Shutdown Wiring; 579F180-300
BP — Building Pressurization:
Evaporator fan on, economizer energized to fully open position,
power exhaust disabled.
E
— Evacuation:
Evaporator fan off, economizer energized to fully open position,
power exhaust on (open).
SD — Complete Unit Shutdown:
Breaks 24-v power to the thermostat.
SP
— Smoke Purge:
Evaporator fan on, economizer energized to fully open position,
power exhaust on.