Form 6104 BCF-35-R0699

Table 5 – Initial air adjusting plate settings

(damper position)

Figure 12 – Air damper and damper motor assembly

Legend (Figure 12)

a Damper motor – do not adjust internal cam

b Arm assembly

c Ball joint assembly – do not adjust position of ball

joint

d Damper rod

e Damper rod guide

f

Damper linkage arm - sets high-fire air position

g Damper

h Damper label - position indicator for air adjusting plate

k Damper indicator - permanently attached to damper

m Air adjusting plate - sets low-fire air position

Approximate

adjusting plate

settings

Firing rate, gph

Tube “KP”

Tube “KM”/“KR”

0

--

--

1

8.00

8.00

2

9.00

9.00

3

11.00

11.00

4

12.00

12.00

5

15.00

15.00

6

17.00

17.00

7

18.00

19.00

8

19.00

22.00

9

20.00

25.00

10

22.00

29.00

10.5

25.00

35.00

CLOSE

OPEN

3516

a

b

d

e

f

g

3517

CLOSE

a

b

d

c

12

0

1

2

3

4

5

6 7

8 9 10 11

h

k

m