SUBJECT OF THIS DOCUMENT: 

Due to the double isolation techniques applied in the Geodesy FSO devices, connecting it into a buildings lightning 
protection, might raise the possibility of the lightning caused damages. In this document we will try to summarize the 
best installation practices how to avoid damages cause by lightning strike. 

OVERVIEW 

The electromagnetic pulse released by a lightning strike or the strike itself is the highest risk, for electrical equipments 
placed outside of buildings.  

The energy of the lightning strikes has to be grounded. This means that the power of the strike should be collected 
and drained to the ground through a network of grounded cables. These cables have to be insulated from the devices 
it protects. 

According to the modern philosophy of the insulated of the insulated lightning protection method to protect the 
equipments from the effects of lightning have to be placed inside of a so called “protected zone”. In this zone the 
equipment is not exposed to the lightning. 

If the system is under the “protection zone” of the insulated lightning protection solution, then it is not necessary, to 
be grounded. The grounding in this case will decrease the protection level as it might open a new path for the energy 
of the lightning to drain. This might make the behaviour of the lightning unpredictable. 

POWER SUPPLY CONSIDERATIONS 

The power supplies are protected on the input and also on the output by fuses, so it won’t pass the large energy of 
the lightning. 

Third party power supplies have to be confirmed by the manufacturer, that it is suitable for powering outdoor 
equipments. 

CABLES 

Data and power cables are also a consideration of the lightning protection. We will try to summarize it. 

OPTICAL CABLES 

Optical cables and patch cords are not conducting electricity, so in the case of fiber cables it is not a subject of 
protection. 

COPPER CABLES 

All copper feeds should be terminated into an approved Ground Fault Interrupters, with surge protection per local 
electrical codes or installation practices. 

 

 