Georgia-Pacific Decorative Wall Panel User Manual

Page 2

Advertising
background image

Tileboard Start installation at an inside corner. Scribe (mark) and

trim panel to fit plumb (vertical). Continue to fit panels making sure

that each successive one is plumb.

Note: Leave a 1/8” caulking space

between panels.

6. Adhesive Application

Adhesive application should be used to apply Hardboard and 1/4”

MDF*. 1/8” and 5/32” MDF requires both adhesive and nails.
Hardboard and MDF Adhesive should be used to apply panels

directly to studs or over existing walls as long as the surface is level,

sound and clean. Once the panel is fitted, apply beads of adhesive

with a caulking gun in a continuous strip along the top, bottom and

both sides of the panel. On intermediate studs, apply beads 3” long

and 6” apart. Over solid backing, apply adhesive in a zigzag pattern

between studs. Some supplemental nailing will be necessary to hold

the panel in place until the adhesive sets. Be sure to read the

adhesive manufacturer’s instructions carefully prior to installation, as

instructions may vary. Use a hammer and padded wood block (or

rubber mallet) to set the glued panel in position.
*Use only a latex water based adhesive with MDF panels. Solvent

based adhesive may cause discoloration of finishes on MDF panels.

7. Cementing — Tileboard only

First, thoroughly clean the surface—sanding if necessary—to ensure

a smooth, tight bond. Clean any dust from the back of the panels.

Do not nail panels in place.
Use a good-quality adhesive and spread according to manufacturer’s

instructions. With a 3/16” notched trowel, scrape the panel so that

you leave only ridges of adhesive covering the entire back surface of

the panel. If you are using moulding, insert prior to setting panels

permanently in place.
Now carefully set the panels in place and press them firmly against the

wall. After 15 minutes press panels again to ensure proper adhesion.

8. Tub and Shower Installation (Tileboard Only)

In addition to the recommendations in section 7, securely seal all

edges and joints with a silicone caulk to prevent water entry. Caulk

all gaps where water or moisture can enter and cause damage to the

product or structure. Apply according to the manufacturer’s instructions.
Installation With a Divider Strip For tileboard installation with

divider strips, leave a 3/16” gap between panels, including 1/16”

between panel edge and the inside of the moulding.
Installation Without a Divider Strip For tileboard installation

without divider strips, seal 1/8” space between panels with a

high-quality silicone caulk. For a pleasing appearance, and a secure

seal, carefully caulk around the tub.

Note: Panel adhesive must be

dry before caulking. Wet adhesive may discolor caulk.

9. Nailing Panels

Hardboard and MDF Panel grooves are usually located every 16”,

allowing nails to be placed in the grooves on standard 16” stud centers.

Panel matching colored ringshank nails are recommended. Use 1”

nails to apply paneling to studs alone, 1-1/2” nails to apply paneling

to a solid backing or plaster. Space nails 6” along panel edges and

8” on intermediate studs. Wear eye protection when nailing.

Tileboard Do not nail tileboard. See Cementing and Tub and

Shower Installation instructions.

10. Installing Paneling over Masonry

NOTE: Not all panels are approved for below-grade use or over

masonry walls. Please consult the instructions printed on the back

of each panel to determine suitability for this application. Excessive

moisture conditions and high humidity will require correction prior to

paneling installation.
NOTE: If installing panels that are less than 1/4” thick, a solid

non-combustible backing such as gypsum wallboard must be placed

over the furring strips before application of the panels.
Quarter inch (1/4”) panels can be applied direct to furring. The

construction of a lightweight wood frame system (furring strips) will

allow paneling to be applied to masonry walls (concrete, brick and

cinder block) or walls in bad repair. Furring strips are 1” x 2” lumber

or 1/2” plywood cut into strips 1-1/2” wide. Strips should run

horizontally 16” apart (based on 8’ ceiling) with vertical members

spaced 48” on center where panels meet. Allow 1/2” space at the

floor and ceiling with the horizontal strips. Check with a level to

make sure each furring strip is flush with the first strip. Use wood

shingles or wedges between the wall and strips to assure a uniformly

flat surface. Furring strips may be applied to a masonry wall with

specially hardened masonry nails. A badly damaged masonry wall may

require the construction of a 2” x 3” stud wall, with 16” stud centers,

before applying panels.
Masonry walls partially or fully below ground level (below grade)

may present a serious dampness problem. Exterior walls must be

insulated and have a 4 mil or greater vapor retarder. Holes or cracks

in masonry walls must be patched with concrete patching compound

and weeping or porous walls must be waterproofed before installing

paneling. In either case, consult the masonry product manufacturer

for specific application instructions.

11. Wainscot Application

For a unique look use wainscoting to combine panel types. An eight-

foot panel cut into thirds will wainscot a 12’ wall to a height of 32”.

Apply wainscoting along lower wall by following instructions for

panel installation. Repeat same steps with the upper wall. Hide the

horizontal seam with a chair rail moulding.

12. Panel Maintenance

Georgia-Pacific pre-finished panels are suitable for normal dry

interior use environments. Georgia-Pacific pre-finished paneling

should not be used in environments where accumulation of grease,

smoke, or other contaminants will require frequent cleaning to

remove accumulations. To remove surface accumulations such as

dust, wipe with a soft cloth dampened with a furniture polish

containing no waxes or silicones. More stubborn accumulations may

require wiping with a soft cloth dampened with a solution of

lukewarm water and a mild liquid detergent. Wipe dry immediately

following this procedure with a clean dry cloth. Tileboard is practi-

cally maintenance-free. It never needs wax and can be cleaned with

a mild soap on a damp cloth or sponge. Never use abrasive cleansers

on panels as it will scratch the finish and dull the panel gloss.

Self-adhering tapes may contain solvents in their adhesives. Applying

to panels may dissolve the protective coating and damage the panel.

2

Advertising