Hda.sae – analog signal iso to hda 5500, Contaminationsensor cs1000 analog output (anaout), Hydac filtertechnik gmbh – HYDAC CS 1000 User Manual
Page 60

ContaminationSensor CS1000
Analog Output (ANAOUT)
HYDAC Filtertechnik GmbH
en
Page 60 / 100
BeWa CS1000 3247149n en 2009-02-04.doc
2009-02-04
HDA.SAE – Analog signal ISO to HDA 5500
The HDA.ISO signal consists of 6 measured values (START / ISO 6 / ISO 6 / ISO 14
/ ISO 21 / Status) which are output sequentially. Synchronization with the
downstream control unit is a prerequisite.
The signal output is as follows:
Time
Measurement
category
Signal duration
in s
Current/Voltage
Start signal 0
--
2
20 mA / 10 V
Pause
2
4 mA / 2 V
Signal 1
ISO 4
2
Current/Voltage for signal
Pause
2
4 mA / 2 V
Signal 2
ISO 6
2
Current/Voltage for signal
Pause
2
4 mA / 2 V
Signal 3
ISO 14
2
Current/Voltage for signal
Pause
2
4 mA / 2 V
Signal 4
ISO 21
2
Current/Voltage for signal
Pause
2
4 mA / 2 V
Signal 5
Status
2
Current/Voltage for signal
Pause
30
4 mA / 2 V