5. Digital

display

After switching on the supply voltage, the unit briefly displays ”ETS” and then displays the
current temperature.

2 s

Notes:
• In the basic settings the display can be altered so that, once switched on, the unit displays a

switching point or the maximum value permanently. In this case ”S.P. 1”, ”S.P. 2”, ”S.P. 3”,
S.P. 4”, or ”MAX” appears briefly on the display following the switch-on message. The
current temperature can be displayed briefly by pressing the ”+” or ”-” key.

• If the current temperature exceeds the nominal temperature of the unit, it can no longer be

displayed and the display begins to flash.

• If the current temperature is below 0.5 °C, then 0 is displayed.

6. Output

function

6.1 Relay

outputs

The ETS 1700 has 4 relay outputs. One switching point and one switch-back point and/or one
hysteresis can be set for each relay. The appropriate relay pulls in when the pre-set switching
point is reached and drops back when the temperature falls below the switch-back point.

Whether the unit operates with adjustable hystereses or adjustable switch-back points is
determined via the ”switch-back mode”, in the basic settings (see Point 8).

Switch-back mode is set to "hysteresis":

The pre-set hysteresis determines the switch-back point (switch-back point = switching point
minus hysteresis).

Switch-back mode is set to ”switch-back point”:

The switch-back point is set directly.