APPENDIX A. DATA TABLES

A.1. Recommended Alarm Settings

Refrigerant

Leak PPM

Spill PPM

Evacuate PPM

R11

100

300

500

R12

100

300

500

R22

100

300

500

R23

100

300

500

R113

100

300

500

R114

100

300

500

R123

25

35

50

R124

100

300

500

R134A

100

300

500

R401A

100

300

500

R402A

100

300

500

R402B

100

300

500

R404A

100

300

500

R407A

100

300

500

R407C

100

300

500

R409A

100

300

500

R410A

100

300

500

R500

100

300

500

R502

100

300

500

R503

100

300

500

R507

100

300

500

R508B

100

300

500

H1301

100

300

500

R408A

100

300

500

FA188

100

300

500

R236FA

100

300

500

N1230

100

300

500

R227

100

300

500

HFP

100

300

500

FC72

100

300

500

R21

100

300

500

R125

100

300

500

H1211

100

300

500

H2402

100

300

500

R245FA

100

300

500

R422A

100

300

500

R422D

100

300

500

R427A

100

300

500

HFO01234YF

100

300

500

R424A

100

300

500

R426A

100

300

500

Ammonia/NH3/R717

100

300

500