Power supply connection details, A b c – Johnson Systems JS-ICON 624 ARCH Dimmer Rack User Manual

Page 7

Advertising
background image

www.johnsonsystems.com

6

www.johnsonsystems.com

7

A B C

A B C

A B C

Three-Phase

Power Supply Input

Earth

Ground

Input

To Phase

Reference PCB

#18 AWG Wire

Factory Wiring To Breakers 1 - 6

#12 AWG Wire

Single-Phase

Power Supply Input

Earth

Ground

Input

To Phase

Reference PCB

#18 AWG

Wire

Factory Wiring To Breakers 1 - 6

#12 AWG Wire

Single-Phase

Power Supply Input

Earth

Ground

Input

To Phase

Reference PCB

#18 AWG

Wire

Factory Wiring To Breakers 1 - 6

#12 AWG Wire

Power Supply Connection Details

The JS-ICON

624 ARCH is capable of various 120V power supply

configurations. Remove the contractor wiring access panel to locate the

contractor termination section, where the required power terminals are

located. Knockouts on the top and bottom of the chassis are provided for

wire/conduit entry to the power terminals.

WARNING: Wiring termination must be done by qualified personnel only!

Power Supply Configurations - Option 1:

Three-Phase with Internal Dimmer/Circuit Breaker Protection

120/208 VAC, 3Ø, 5-Wire up to 40 Amps per phase. Maximum 14.4kW total.
Use #2 to #12 AWG copper wire only, rated for 90°C minimum.

Torque power connections (A, B, C) to 5.0-5.6 NM (45-50 LB-IN).

Torque ground lug connection to 5.6 NM (50 LB-IN).

• Dimmers 1 and 2 are powered from Phase A.

• Dimmers 3 and 4 are powered from Phase B.

• Dimmers 5 and 6 are powered from Phase C.

NOTE: Power supply requires an external disconnect.

Power Supply Configurations - Option 2:

Single-Phase with Internal Dimmer/Circuit Breaker Protection

120/240 VAC, 1Ø, 4-Wire up to 60 Amps per phase. Maximum 14.4kW total.
Use #2 to #12 AWG copper wire only, rated for 90°C minimum.

Torque power connections (A, C) to 5.0-5.6 NM (45-50 LB-IN).

Torque ground lug connection to 5.6 NM (50 LB-IN).

• Dimmers 1, 2, and 3 are powered from Phase A.

• Dimmers 4, 5, and 6 are powered from Phase C.

NOTE: Power supply requires an external disconnect.

Three-Phase to Single-Phase Conversion

JS-ICON

systems are shipped from the factory ready for three-phase

operation unless otherwise specified at the time of purchase. The following

steps will need to be followed to convert the JS-ICON

from three-phase

operation to single-phase operation.

1. Remove wire #3 (red #12AWG wire, marked with black heat-shrink)

going from the B power terminal to breaker #3, and reconnect to A

power terminal (dimmers 1, 2, and 3 are now connected to Phase A).

2. Remove wire #4 (red #12AWG wire, marked with blue heat-shrink)

going from the B power terminal to breaker #4 and reconnect to C

power terminal (dimmers 4, 5, and 6 are now connected to Phase C).

3. Reconnect the red #18AWG phase reference wire to the B power

terminal.

NOTE: Be sure to set the 3-Phase/1-Phase select switch (located on the
Phase Reference Printed Circuit Board) to the correct position to ensure
proper dimming.